Section 7: Operating Instructions
This chapter provides all the information necessary for the operator to carry out main operations on
the H-S81-HS control panel. This section includes some basic operations, such as:
•
Silencing the control panel
•
Silencing the sounders
•
Resetting the control panel
•
Displaying multiple events
•
Enabling/disabling a system section
•
Viewing the zone and device statuses
•
Testing the control panel or the zones.
•
Setting date and time
•
Configuring control panel parameters
7.1 Operator Interface
The operator interface of the H-S81-HS control panel includes: a graphic display, 14 indicator
LEDs, and a 23-key keyboard.
7.1.1 Visual Indicators
ALARM LED (fire alarm function)
It flashes when an alarm status is received from one input defined as fire when programming. It is
steady on if Control panel silencing is commanded. It goes out in case of reset.
GENERAL TROUBLE LED (burglar/fire alarm function)
It flashes in case of any troubles. It goes out when the cause of the problem is solved or further to
the reset command if the cause has ceased to exist.
DEVICE TROUBLE LED (fire alarm function)
It flashes in case of sensor or actuator (other than sounders) troubles. It goes out when the cause of
the problem is solved or further to the reset command if the cause has ceased to exist.
SOUNDER TROUBLE LED (fire alarm function)
It flashes in case of troubles of actuators defined as sounders. It goes out when the cause of the
problem is solved or further to the reset command if the cause has ceased to exist.
128
Figure 7.1 Operator Interface
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015