Notes for the Development of Systems in Compliance with the EN12094-1 Standard

6.2.8 Receiving and Processing Inbound Actuation Signals

The system is able to receive an automatic actuation signal from the detection modules and a man-
ual actuation signal from the manual actuation devices connected to S81-F3002 type modules.
NOTE: After receiving the actuation signal "Activated" condition), no disabling operation can be
carried out in the relevant fire suppression zone.
6.2.9 Transmission of the Release Signal
After receiving the actuation signal, the system transmits the signal to releasing devices (sole-
noids). Signal transmission (actuation) only affects the selected bank (main/reserve).
6.2.10 Actuation of Alarm Devices
After receiving the actuation signal, the system transmits the signal to Alarm devices.
NOTE: Alarm devices can be silenced at access level 2 (sounder silencing) only after the
"released" condition has activated.
6.2.11 Main Voltage Detection Signal
The main voltage detection signal relates to the whole system (Power-ON LED on the display).

6.2.12 "Activated" Condition

The system sets in "Activated" condition within one seconds from the receipt of inbound actuation
signals. After setting the "Activated" condition, the d.e.c. always activates alarm devices within
one second. The "Activated" condition is signaled by:
Activation of local audible indication
Activation of the "Activated" zone steady light indicator on module S81-F6001
Intermittent activation of alarm device control output. (TOA)

6.2.13 "Released" Condition

The "released" condition is activated when the signal relating to extinguishing agent flow (PSH) is
received or when releasing devices (EV) output is activated. When programming, the user can
decide how to set the "released" condition. The "released" condition is signaled by:
Activation of the "released" zone steady light indicator on module S81-F6001
Activation of the output for "released" condition replication.
Continuous activation of alarm device control output. (TOA)
If the "released" condition is activated further to the receipt of the signal relating to extinguishing
agent flow without the d.e.c. being in the "Activated" condition (Manual release by mechanical
command) the local sounder is also activated.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015