Configuration; Threshold Setting - Honeywell H-S81-HS Operation Manual

Industrial fire panel
Hide thumbs Also See for H-S81-HS:
Table of Contents

Advertisement

Parts of the H-S81-HS System
Three-Digit Display
The three-digit display generally shows the measured value in the programmed format. Moreover,
it shows some fault codes according to the following table.
No.
---
F00
F01
F02
F03
Fx.x
E00
+/-999
1 For current values lower than the set trouble threshold and exceeding 1mA, the
display will show the value of the measured current in mA preceded by letter F. Please
refer to the manual of the connected device for identifying the type of anomaly.
NOTE: The 3-digit display on module front panel does not provide the operator with fundamental
information and does not comply with the standard EN-54-2.

Configuration

By using the configuration program ProS81, the following parameters can be set for each input
channel:
Function
Operating mode
Mode of analog value transfer to Hosts
Unit of measure of the channel
Zero Point of the measuring range
End of scale of the measuring range
Pre-alarm threshold
Alarm threshold
Lower trouble threshold
Alarm delay
Type of indication
Automatic alarm reset
Enable/Disable status export via ModBus
Enable/Disable channel status export to Hosts
Enable/Disable commands from Hosts on the channel
It defines the format of the analog value sent via ModBus,
and automatically via Host

Threshold Setting

The following parameters can be set for each module through the configuration program or directly
on the control panel in the operator cycle, access level 3:
Pre-alarm threshold.
Alarm threshold
Current value below which a trouble condition is signaled
Calibration mixture concentration value for end of scale calibration
50
Channel Status
Initialization stage
Module/channel not configured
Line opening (current <1mA)
Over-current (current >23.5mA)
Internal test failed
1
Device trouble
Memory data error CRC
Measured value
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Allowed values
Latching/Non latching, UP/Down, NM
Upon request/Automatic in case of change
Ppm, %LEL, %O2, mA, °C, RH, V, bar, db, rpm
-999 - 999
-999 - 999
-999 - 999
-999 - 999
1,0 - 3,8mA
0 - 255 seconds
Fire, Supervisory, Gas, Trouble, Hidden, Buzzer Only
Yes/No
Yes/No
No, TCP1, TCP2, RS232
No, TCP1, TCP2, RS232
mA, mA tenth, VI, VI tenth, converter points
I/O modules