Notes on I/O Module Redundancy
6.4.1 I/O Module Redundancy
I/O module redundancy means the possibility to connect a field user to two modules at the same
time. Therefore, redundancy in this document refers to I/O modules only, and not to field devices.
With respect to this, we would remind that complete redundancy (modules + field devices) is possi-
ble for all I/O modules without restrictions. The I/O modules of the H-S81-HS system can be
divided into two categories:
Redundancy not possible
Redundancy possible, with restrictions
6.4.2 I/O Modules for Which Redundancy is Not Possible
Redundancy is not possible for these modules:
• S81-F5002-1
• S81-F5003-1
• S81-F6001-1
• S81-F6002-1
• S81-F7002-1
• S81-F7006-1
• S81-F7007-1
• S81-F7008-1
• S81-F7009-1
• S81-F7010-1
1 The module S81-F7006 cannot be duplicated, but features two independent communi-
cation lines, one RS485 and one RS232; therefore, the communication to the DCS can
be considered redundant.
6.4.3 I/O Modules for Which Redundancy is Possible With
Restrictions
Redundancy is possible for the modules below, with some restrictions or precautions:
S81-F3002-2 Module with 8 safety related monitored inputs
These modules can be redundant, even though with the following restrictions:
To isolate an input line, both channels connected to that line shall be isolated.
In the supervisory system, each sensor shall be represented by two different items.
Modules shall be placed on adjacent racks and in the same position.
Duplicated channels shall be configured in the same way.
S81-F4001-2, S81-F4002-2, S81-F4003-2 4-20mA safety related modules
These modules can be redundant, even though with the following restrictions:
To isolate an input line, both channels connected to that line shall be isolated.
In the supervisory system, each sensor shall be represented by two different items.
Modules shall be placed on adjacent racks and in the same position.
Duplicated channels shall be configured in the same way.
S81-F5001 S81-F5004-2 Safety related output modules
These modules can be redundant, even though with the following restrictions:
To isolate an output line, both channels connected to that line shall be isolated.
In the supervisory system, each actuator shall be represented by two different items.
Modules shall be placed on adjacent racks and in the same position.
Duplicated channels shall be configured in the same way.
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Module with 16 non monitored outputs
Module with 8 monitored outputs with polarity reversal for audible alarm devices
Control module for fire extinguishing systems
Logic module
ESP protocol control module
Modbus RTU Master/Slave module
SSP protocol control module
Control module for scales
Apollo protocol control module
System Sensor protocol control module
1
Application Notes
127