4.2 Electrical specifications

External power supply: 100 ... 240 V AC, 50 ... 60 Hz
AC Fuse: 4 A / 250 Vac / 5 x 20 mm (slow blow)
Power consumption: max. 65 W
2  Supervised sounder outputs each with max. 250 mA
1  24 V DC, User load max. 500 mA
2  Digital Inputs
1  Alarm relay C/NC/NO dry contacts
1  Fault relay C/NC/NO dry contacts
Max. 1.500 m distance depending on the cable section and current consumption in alarm
Rmax battery: 1,4 Ohm
Battery fuse: 4 A / 250 Vac / 5 x 20 mm (fast acting)

4.3 Environmental specifications

Climate classification: K5 (IEC 721-2-3)
Temperature range: -5 ºC ... 40 ºC
Relative humidity: 5 % ... 95 % non-condensing
Protection rating: IP 30 (acc. EN 60529)