7.3 Optional Loop Module (PL-LIB-01) - Installation Overview

The Optional Loop Module PL-LIB-01 add an additional loop the PL-1000 FACP, expanding the system up two loops in total. The loop supports up to 159 detectors
plus 159 input / output modules.
The Module is fixed in the back box, beyond the main board, with the 8 plastic spacers. The ribbon cable grants the electrical connection to the main board.
Fig.18: Optional Loop Module connection with accessories
The PL-LIB-01 kit includes:
8 x plastic spacer .
1 x 20 pole ribbon cable 
M-169.1-SERIE-PL-EN / 09.2022
Installation
1. Put the plastic spacers  into the predisposed holes  on the back box.
2. Connect the ribbon cable  on the Loop Module PL-LB-01.
3. Install the Loop Module onto the plastic spacer .
4. Connect the ribbon cable  to the main board.
2
nd
Loop Connection 
Loop 2  A+
Loop 2  A -
Loop 2  B+
Loop 2  B-
Fire Alarm Control Panel PL-1000