Product Description

1.4 Controls and Indicators

16
LCD Display
The FACP uses an 80-character (4
lines X 20 characters) high viewing
angle LCD display. The display
includes a long life LED backlight
that remains illuminated. If AC
power is lost and the system is not in
alarm, the LED backlight will turn off to conserve batteries.
LED Indicators
LED indicators are provided to annunciate the following conditions:
AC Power (green)
Fire Alarm (red)
Supervisory (yellow)
Trouble (yellow)
Maintenance/presignal (yellow)
Alarm Silenced signals (yellow)
Disabled (yellow)
Battery fault (yellow)
Ground fault (yellow)
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD
display and LED indicators as listed above. The key panel, which is visible with the
cabinet door closed, has 25 keys, including a 16 key alpha-numeric pad similar to a
telephone keypad.
Function keys:
Acknowledge/Step
Alarm Silence
Drill
Reset (lamp test)
Service/program keys:
Keys labeled 1 to 9
* key
# key
0 (recall) key
1st Event key
Clear key
Escape key
Mode key
Four cursor keys (up, down, left and right)
Enter key
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and
supervisory conditions.
Controls and Indicators
FIRE-LITE ALARMS INC
SYSTEM ALL NORMAL
10:00A 020102
AC POWER
FIRE ALARM
SUPERVISORY
1
2
3
1
st
ABC
DEF
EVENT
4
5
6
CLR
ENTER
GHI
JKL
MNO
ESC
7
8
9
TUV
WXY
PRS
MODE
*
0
#
-/.
QZ
RECALL
Figure 1.2 Membrane/Display Panel
MS-9600 PN 51335:E1 2/14/08
MAINTENANCE
ALARM
SILENCED
DISABLED
TROUBLE
BATTERY
GROUND
ACK/STEP
ALARM
SILENCE
DRILL
HOLD 2 SEC
RESET