Omron VS mini J7 User Manual page 116

Compact general purpose inverter
Hide thumbs Also See for VS mini J7:
Table of Contents

Advertisement

DSR Message and Response
Response
Normal
Byte No.
1
Slave address
2
Function code (03 Hex)
3
Number of bytes of attached data
4
Data of start register
5
6
Data of next register
7
8
Data of next register
9
:
:
n–1
CRC-16 check
n
Error
Byte No.
1
Slave address
2
Function code (83 Hex)
3
Error code
4
CRC-16 check
5
Example of Data Read
DSR Message
Byte No.
1
Slave address
2
Function code
3
Register No. of read start data
4
5
Number of registers of read data
6
7
CRC-16 check
8
102
Note
When an error occurs, the MSB of the function code will be set to 1.
In the following example, four-register data (status signal data) is read from
register 0020 Hex of the Inverter with a Slave address of 02.
Data
Data
Data
Chapter 7-4
MS B
LSB
MSB
LSB
MSB
LSB
:
Data example
(Hex)
02
03
00
20
00
04
45
F0