Omron VS mini J7 User Manual page 100

Compact general purpose inverter
Hide thumbs Also See for VS mini J7:
Table of Contents

Advertisement

Other Functions
Set Values
Value
0
The frequency on hold is not retrained.
1
The frequency on hold for 5 s or more is retailed.
Operation of UP/DOWN Function
RUN command
(Forward rotation)
UP command
(S4)
DOWN command
(S5)
Output frequency
Upper limit
Lower limit
Status
Frequency
detection
Note
Command
S4 (UP command)
S5 (DOWN command)
86
Status
U: UP (acceleration)
D: DOWN (deceleration)
H: Hold
U1: Frequency acceleration restricted by upper limit.
D1: Frequency deceleration restricted by lower limit.
The following ON/OFF combinations of UP and DOWN commands are
possible.
Acceleration
ON
OFF
With the UP/DOWN function used, the output frequency has the following
restrictions for upper and lower limits.
Upper limit: The maximum frequency in n09 or the frequency reference
upper limit in n30, whichever is smaller.
Lower limit: The minimum output frequency in n14 or frequency reference
lower limit in n31, whichever is smaller.
Description
Deceleration
OFF
OFF
ON
OFF
Chapter 6-7
Time
Time
Time
Time
Time
Hold
Hold
ON
ON

Hide quick links:

Advertisement