Register Number Allocations in Detail
Broadcast Message with Slave Address: 00 (00 Hex) Write
Register No. (Hex)
0000
Not used.
0001
RUN command
0002
Frequency reference
0003 to 000F
Not used.
RUN Command (Register 0001 Hex)
Bit No.
0
1
2 to 3
4
5
4 to 15
7-7-2

Monitor Functions

Register No. (Hex)
0020
Status signal
0021
Fault status
0022
Data link status
0023
Frequency reference
0024
Output frequency
0025 to 0026
Not used.
0027
Output current
0028
Output voltage
0029 to 002A
Not used.
002B
Input terminal status
002C
Inverter status 1
002D
Output terminal status
002E to 0030
Not used.
0031
Main circuit DC voltage
0032 to 003C
Not used.
003D
Communications error
003E to 00FF
Not used.
112
Function
Note
1. Data can be written to registers 0001 and 0002 only. Assumed previous
values are held for unused registers.
2. No data can be written to multi-function input.
3. The unit of setting of the broadcast message is different from that in the
DSR message to communicate with a single Slave.
RUN command (1: RUN)
Forward/Reverse (1: Reverse)
Not used.
External fault (1: External fault EF0)
Fault reset (1: Fault reset)
Not used.
Function
Description
---
Refer to the table below.
Set the frequency reference based on the maximum
frequency as 30,000.
---
Function
Description
Refer to the following corresponding table.
Refer to the following corresponding table.
Refer to the following corresponding table.
According to the set value in n69.
According to the set value in n69.
---
Read based on 1 A as 10.
Read based on 1 V as 1.
---
Refer to the following corresponding table.
Refer to the following corresponding table.
Refer to the following corresponding table.
---
Read based on 1 V as 1.
---
Refer to the following corresponding table.
---
Chapter 7-7