Siemens SIPROTEC 7UT613 series Manual page 78

Differential protection
Hide thumbs Also See for SIPROTEC 7UT613 series:
Table of Contents

Advertisement

2 Functions
Voltage Transform-
er Data
78
Table 2-4
Terminal designation with surface mounted housing
Corresponds to surface mounted housing, terminal 1-phase current
Flush mounted
housing
7UT613
Terminal Q7
Terminal Q8
Terminal N7
Terminal N8
Terminal R7
Terminal R8
Terminal P7
Terminal P8
If the device is equipped with measuring voltage inputs and these inputs are assigned,
the voltage transformer data are of relevance.
For the 3-phase voltage input, you set at address 801 UN-PRI VT SET the primary
rated VT voltage (phase-to-phase), and at address 802 UN-SEC VT SET the second-
ary rated VT voltage.
If the reverse power protection with high-precision active power measurement is used,
a correction of the angle faults of the current and voltage transformers is particularly
important, as in this case a very low active power is computed from a very high appar-
ent power (for small cos ϕ). In other cases, absolute compliance with the angle of mea-
sured values is usually not required. In 7UT613/63x angle errors are corrected in the
voltage paths. The question of which current transformer set refers to the correction,
is thus irrelevant, and an influence on the currents for differential protection and all
current functions by this correction is avoided. All power functions are corrected on the
other side. The angle correction is not important to the pure voltage functions (overex-
citation protection, undervoltage protection, overvoltage protection, frequency protec-
tion), as the precise phase angle of the voltages is not relevant there. Set the resulting
angle difference of the current and voltage transformers relevant for the reverse power
protection under address 803 CORRECT. U Ang. In electrical machines, determina-
tion of the corrective value is possible at primary commissioning of the machine.
For the 1-phase voltage input, you set at address 811 UN-PRI VT U4 the primary
rated voltage of the connected 1-phase voltage transformer, and at address 812 UN-
SEC VT U4 the secondary voltage. The addresses 811 and 812 must be set if the U4
transformer set has a different reference than the VT SET.
If the single-phase voltage input of a U4 transformer is a Uen transformer and equally
assigned like the main transformer set, then a different transformation ratio of the
single-phase voltage transformer from the three-phase voltage transformer set can be
set under address 816 Uph / Udelta. If the single-phase voltage input at the open
delta winding e-n of the voltage transformer set is connected, the voltage transforma-
tion of the transformer is normally as follows:
Factor Uph/Uen (secondary voltage) 3/sqrt(3) = √3 ≈ 1.73 must be used. For other
transformation ratios, e.g. if the residual voltage is formed by an interposed transform-
er set, the factor must be adapted accordingly. This factor is of importance for the
monitoring of the measured values and the scaling of the measurement and distur-
bance recording signals.
7UT633
22
47
47
97
11
36
36
86
18
43
43
93
input
7UT635
47
IX1
97
36
IX2
86
43
IX3
93
32
IX4
82
7UT613/63x Manual
C53000-G1176-C160-2