Siemens SIPROTEC 7UT613 series Manual page 358

Differential protection
Hide thumbs Also See for SIPROTEC 7UT613 series:
Table of Contents

Advertisement

3 Mounting and Commissioning
358
The input/output board C-I/O-2 carries the following measured current inputs:
• For 3-phase applications and 1-phase transformers:
There are 3 measuring inputs for the three-phase measuring location M3: I
I
, I
. The jumpers X61, X62, X63 belonging to this measuring location must
L2M3
L3M3
be plugged all to the rated secondary current of the connected current transformers:
„1A "or „5A". Furthermore, the corresponding common jumpers (X51 and X60) have
to be plugged to the same rated current.
• For 1-phase busbar protection:
There are 3 measuring inputs for 3 different measuring locations, i.e. the feeders 7
to 9: I
, I
, I
. Each input can be set individually (X61, X62, X63) to „1A", „5A" or
7
8
9
„0.1A". Only if the measuring inputs I7 to I9 have the same rated current, the
common jumpers X60 are plugged to this rated current.
If different rated currents (X51 and X60) are reigning within the input group, the po-
sition of the common jumpers (X51 and X60) is irrelevant.
• For the additional single-phase measuring input I
Jumper X64 is set to the required rated current for this 1-phase current input: „1A"
or „5A".
Table 3-14
Jumper setting for nominal current or measuring range
Jumper
Nominal current 0.1 A
Measuring range
X51
X60
X61
X62
X63
X64
Nominal current 1 A
Measuring range
10 A
2-3
1-2
1-5
1-5
1-5
1-5
:
X2
Nominal current 5 A
Measuring range
100 A
1-2
1-2
3-5
3-5
3-5
3-5
7UT613/63x Manual
C53000-G1176-C160-2
,
L1M3
500 A
1-2
2-3
4-5
4-5
4-5
4-5