7UT613/63x Manual
C53000-G1176-C160-2
Table 3-2
Jumper settings of the rated voltage of the integrated Power Supply on the C-
CPU-2 processor board
Jumper
24 to 48 VDC
X51
Not used
X52
Not used
X53
Not used
X55
Not used
Cannot be changed
Fuse
T4H250V
Table 3-3
Jumper setting of the pickup voltages of the binary inputs BI1 to BI5 on the C-
CPU-2 processor module
Binary Inputs
Jumper
BI1
X21
BI2
X22
BI3
X23
BI4
X24
BI5
X25
1)
Factory settings for devices with rated power supply voltage 24 to 125 VDC
2)
Factory settings for devices with rated power supply voltage 110 to 250 VDC and 115 to 230
to 250 VAC
3)
Only for control voltage 200 VDC or 250 VDC
Table 3-4
Jumper setting of the quiescent state of the Life Contact on the processor
board C-CPU-2
Jumper
Open in the quiescent
X40
By repositioning jumpers the interface RS485 can be modified into a RS232 interface
and vice versa.
Jumpers X105 to X110 must be set to the same position.
Table 3-5
Jumper settings of the integrated RS232/RS485 Interface on the C-CPU-2 pro-
cessor board
Jumper
X103 and X104
X105 to X110
The jumpers are preset at the factory according to the configuration ordered.
With interface RS232 jumper X111 is needed to activate CTS which enables the com-
munication with the modem.
Nominal voltage
60 to 125 VDC
1-2
1-2 and 3-4
1-2
not used
1)
Threshold 19 V
1-2
1-2
1-2
1-2
1-2
Closed in the quiescent
state
1-2
RS232
1-2
1-2
3.1 Mounting and Connections
110 to 250 VDC,
220 to 250 VDC,
115 to 230 VAC
115 to 230 VAC
2-3
2-3
2-3
1-2
Interchangeable
T2H250V
2)
Threshold 73 V
Threshold 154 V
2-3
2-3
2-3
2-3
2-3
state
2-3
RS485
1-2
2-3
2-3
2-3
2-3
1-2
3)
3-4
3-4
3-4
3-4
3-4
Presetting
2-3
351