Siemens SIPROTEC 7UT613 series Manual page 488

Differential protection
Hide thumbs Also See for SIPROTEC 7UT613 series:
Table of Contents

Advertisement

4 Technical Data
Operational values for
power
(3-phase, if voltage
connected)
Operational measured
values for power
(1–phase, with measured
or rated voltage)
Operational values for
power factor
(3-phase, if voltage
connected)
Operational measured
values for
thermal value
(overload protection acc. to
IEC 60255-8)
Operational measured
values for
thermal value
(overload protection acc. to
IEC 60354)
Tolerances are based on the preset matching parameters. Higher tolerances are to be expected for calculated
values dependent on the matching factors for currents and voltages.
Measured values of differ-
ential protection
Measured values of restrict-
ed earth fault protection
Tolerances are based on the preset matching parameters for a protected object with 2 sides and 1 measuring lo-
cation on each side. Higher tolerances are to be expected for calculated values dependent on the matching factors
for currents and the number of measuring locations.
Fault Logging
488
Active power P; reactive power Q; apparent power S in kW; MW; kVA; MVA primary
– Tolerance
S (apparent power) in kVA; MVA primary
cos ϕ
Θ
; Θ
; Θ
; Θ
referred to tripping temperature rise θ
L1
L2
L3
res
Θ
to Θ
in °C or °F relative ageing rate, load reserve
RTD1
RTD12
I
; I
; I
; I
; I
diffL1
diffL2
diffL3
restL1
in % of the operational nominal current
– Tolerance (with preset values)
(for 2 sides with 1 measuring location
each)
I
; I
in % of the operational nominal current
diffREF
restREF
– Tolerance (with preset values)
(for 1 side or 1 measuring location)
Storage of the messages of the last
8 faults
1.2 % of measured value, or 0.25 % of S
; I
;
restL2
restL3
2 % of measured value, or 2 % I
(50/60 Hz)
3 % of measured value, or. 3 % I
(16.7 Hz)
2 % of measured value, or 2 % I
(50/60 Hz)
3 % of measured value, or. 3 % I
(16.7 Hz)
with a total of max. 200 messages
trip
N
N
N
N
7UT613/63x Manual
C53000-G1176-C160-2