Siemens SIPROTEC 7UT613 series Manual page 388

Differential protection
Hide thumbs Also See for SIPROTEC 7UT613 series:
Table of Contents

Advertisement

3 Mounting and Commissioning
Message
„U< err. VT"
033.2492 Undervoltage protection is not available without voltage connection 2.14
„U< err. Set."
033.2493 Undervoltage protection setting not plausible
„U> err. Obj."
034.2491 Overvoltage protection is not available for the configured protected
„U> err. VT"
034.2492 Overvoltage protection is not available without voltage connection
„U> err. Set."
034.2493 Overvoltage protection setting not plausible
„Freq. err. Obj."
5255
„Freq. error VT"
5254
„Freq. err. Set."
5256
„Pr obj. error"
5101
„Pr CT Fact ><"
5099
„Pr VT error"
5100
„Pr set error"
5102
„Pf> Object err"
5132
„Pf> CT fact ><"
5130
„Pf> VT error"
5131
„Pf> set error"
5133
BrkFail not av.
1488
047.2493 Breaker failure protection setting not plausible
„BkrFail2 Not av"
206.2491 Breaker failure protection is not available for the configured protected
„BkrFail2 errSet"
206.2493 Breaker failure protection setting not plausible
„TripC ProgFail"
6864
388
No
object
Frequency protection is not available for the configured protected
object
Frequency protection is not available without voltage connection
Frequency protection setting not plausible
Reverse power protection is not available for the configured protect-
ed object
The matching factor of the current transformers for reverse power
protection is too great or too small.
Reverse power protection is not available without voltage connection 2.12
Reverse power protection setting not plausible
Forward power supervision is not available for the configured protect-
ed object
The matching factor of the current transformers for forward power su-
pervision is too great or too small.
Forward power supervision is not available without voltage connec-
tion
Forward power supervision setting not plausible
Breaker failure protection is not available for the configured protected
object
object
For trip circuit supervision the number of binary inputs was set incor-
rectly
In the operational or spontaneous annunciations also check if there are any fault an-
nunciations from the device.
The matching factors of all measured value inputs are indicated in the operational an-
nunciations. It is recommended to check these factors even if none of the above men-
tioned alarms is present. The indicated factors are:
• generally, the ratio of the rated current/voltage of the side referred to the rated cur-
rent/voltage of the instrument transformers at the measuring locations;
• for differential protection, the ratio of the rated current of the protected object re-
ferred to the rated current of the current transformers at the measuring locations;
• For restricted earth fault protection, the ratio of the rated current of the assigned
side of the protected object referred to the rated current of the starpoint current
transformer.
None of these factors should be greater than 8 or smaller than 0.125. Otherwise, the
risk of higher measuring errors could arise. If a factor is greater than 50 or smaller than
0.02, unexpected reactions of protection function may occur.
Meaning
see
Section
2.14
2.15
2.15
2.15
2.16
2.16
2.16
2.12
2.12
2.12
2.13
2.13
2.13
2.13
2.1.4
2.1.4
2.1.42.1.6
2.1.4
3.1
(„Connection Vari-
ants")
7UT613/63x Manual