Siemens SIPROTEC 7UT613 series Manual page 357

Differential protection
Hide thumbs Also See for SIPROTEC 7UT613 series:
Table of Contents

Advertisement

7UT613/63x Manual
C53000-G1176-C160-2
Table 3-11
Jumper setting for the contact type of the relay for BO6 to BO8
for
Jumper
BO6
X41
BO7
X42
BO8
X43
1)
Delivery state
The relay contacts for binary outputs BO1 through BO5 can be connected to common
potential, or configured individually for BO1, BO4 and BO5 (BO2 and BO3 are without
function in this context) (see also General Diagrams in the Appendix A.2).
Table 3-12
Jumper settings for the configuration of the common potential of BO1 through
BO5 or for configuration of BO1, BO4 and BO5 as single relays
Jumper
BO1 to BO5
connected to common potential
X80
1-2, 3-4
X81
1-2, 3-4
X82
1)
Delivery state
Jumpers X71 through X73 on the input/output board C-I/O-2 serve for setting the bus
address. Their position may not be changed. The following table shows the preset
jumper positions.
Table 3-13
Jumper Position of the Module Addresses of the input/output board C-I/O-2
Jumper
Presetting
X71
1-2 (H)
X72
1-2 (H)
X73
2-3 (L)
The rated currents of the measured current inputs can be determined for each ana-
logue input via jumpers. With default settings all jumpers are set to the same rated
current (according to the order number of the device).
Quiescent state open
1)
(close)
1-2
1-2
1-2
BO1, BO4, BO5 configured as single relays
1)
2-3
3.1 Mounting and Connections
Quiescent state closed
(open)
2-3
2-3
2-3
(BO2 and BO3 without function)
2-3, 4-5
2-3, 4-5
1-2
357