Voltage Symmetry
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-114
Current Symmetry Monitoring
In healthy network operation it can be expected that the voltages are nearly balanced.
If measured voltages are connected to the device, this symmetry is checked in the
device by magnitude comparison. To do this, the phase-to-earth voltages are mea-
sured. The lowest phase-to-earth voltage is set in relation to the highest. An imbalance
is detected when
| < BAL. FACTOR U as long as |U
|U
|/|U
min
max
TherebyU
is the largest of the three phase-to-phase voltages and U
max
The symmetry factor BAL. FACTOR U is the measure for the asymmetry of the con-
ductor voltages; the limit value BALANCE U-LIMIT is the lower limit of the operating
range of this monitoring (see Figure Voltage Symmetry Monitoring). Both parameters
can be set. The dropout ratio is about 95 %.
This malfunction is reported as „Fail U balance".
Figure 2-115
Voltage Symmetry Monitoring
2.19 Monitoring Functions
| > BALANCE U-LIMIT
max
the smallest.
min
281