Siemens SIPROTEC 7UT613 series Manual page 483

Differential protection
Hide thumbs Also See for SIPROTEC 7UT613 series:
Table of Contents

Advertisement

Device-specific Limits
Additional Limits
Maximum number of TICKS in the priority classes
7UT613/63x Manual
C53000-G1176-C160-2
Designation
Maximum number of inputs of one
chart for each task level (number of
unequal information items of the left
border per task level)
Maximum number of reset-resistant
flipflops
D_FF_MEMO
Designation
Maximum number of synchronous
changes of chart inputs per task level
Maximum number of chart outputs per
task level
Additional Limits
Sequence
Level
TIMER
MW_PROC
PLC1_PROC
PLC_PROC
SFS_PROC
1)
When the limit is exceeded, an error message is issued by the device. Consequently, the
device is put into monitoring mode. The red ERROR-LED lights up.
2)
TIMER and TIMER_SHORT share the available timer resources. The relation is TIMER = 2
· system timer and TIMER_SHORT = 1 · system timer. For the maximum used timer number
the following side conditions are valid: (2 · number of TIMERs + number of TIMER_SHORTs)
< 30. The LONG_TIMER is not subject to this condition.
3)
The time values for the blocks TIMER and TIMER_SHORT must not be smaller than the time
resolution of the device, i.e. 5 ms, otherwise the blocks will not start with the starting impulse
issued.
Sequence Level
MW_BEARB (Measured Value Processing)
PLC1_PROC (slow PLC processing)
PLC_PROC (fast PLC processing)
SFS_PROC (interlocking)
1)
When the sum of TICKS of all blocks exceeds the limits before-mentioned, an error indication
is output by CFC.
Limit
400
Only fault annunciation (record in device
fault log); here the number of elements of
the left border per task level is counted.
Since the same information is indicated at
the border several times, only unequal infor-
mation is to be counted.
350
When the limit is exceeded, an error
message is output by the device. Conse-
quently, the device is put into monitoring
mode. The red ERROR-LED lights up.
Limit
50
When the limit is exceeded, an error
message is output by the device. Conse-
quently, the device is put into monitoring
150
mode. The red ERROR-LED lights up.
1)
for the Following 4 CFC Blocks
2) 3)
TIMER_SHORT
15
30
4.20 User-defined Functions (CFC)
Comments
Comments
2) 3)
CMD_CHAIN
D_FF_MEMO
20
Limits in TICKS
10000
2000
200
10000
350
1)
483