Siemens SIPROTEC 7UT613 series Manual page 143

Differential protection
Hide thumbs Also See for SIPROTEC 7UT613 series:
Table of Contents

Advertisement

7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-59
Principle of Restricted Earth Fault Protection
For auto-transformers 3I
nected winding (full winding and tap(s)).
When an earth fault occurs outside the protected zone, another earth currents flows
through the phase current transformers. This is, on the primary side, in counter-phase
with the starpoint current and has equal magnitude. The maximum information of the
currents is evaluated for restraint: the magnitude of the currents and their phase posi-
tion. The following is defined:
a tripping effect current
I
= |3I
'|
from
0
and the stabilisation or restraining current
I
= k · ( |3I
' – 3I
"| – |3I
stab
0
0
k is a stabilisation factor which will be explained below, at first we assume k = 1. I
produces the tripping effect quantity, I
To clarify the situation, three important operating conditions with ideal and matched
measurement quantities are considered:
" is valid as the sum of all phase currents flowing to auto-con-
0
' + 3I
"| )
0
0
counteracts this effect.
stab
2.3 Restricted Earth Fault Protection