Siemens SIPROTEC 7UT613 series Manual page 541

Differential protection
Hide thumbs Also See for SIPROTEC 7UT613 series:
Table of Contents

Advertisement

7UT613/63x Manual
C53000-G1176-C160-2
Mismatching factor for 7UT613/63x, (limited resolution of the measurement)
where:
I
= rated current of the protected object
nO
(in relation to the parameterised rated current)
U
= parameterised rated current of the protected object
nO
I
= nominal device current
Nrelay
S
= maximum (rated) power of the protected object
Nmax
(for transformers: side with the largest (rated) load)
Caution: If earth fault differential protection is used, the requirement for the phase
current transformer of the REF side is as follows:
≤ F
1
former remains
/
8
Adap
Figure A-30
CT verification for Devices 7UT613/63x
The CB layout within the power station unit is not specified.
x"
= sub-transient direct-axis reactance of the generator in p.u.
d
U
= transformer short-circuit voltage HV - LV in %
k
= assumed with 0.1 Ω, (the consumption of the above devices is below
R
relay
0.1 VA)
A.4 Current Transformer Requirements
1
≤ 8)
≤ F
≤ 4, (for the starpoint trans-
/
4
Adap
541