Differential protection
Hide thumbs Also See for SIPROTEC 7UT613 series:
Table of Contents

Advertisement

Addr.
Parameter
7622
MiMa RESET TIME
7623
MiMa RESETCYCLE
7624
MinMaxRES.START
8101
BALANCE I
8102
BALANCE U
8104
SUMMATION U
8105
PHASE ROTAT. I
8106
PHASE ROTAT. U
8111
BAL. I LIMIT M1
8112
BAL. FACT. I M1
8113A
T Sym. I th. M1
8121
BAL. I LIMIT M2
8122
BAL. FACT. I M2
8123A
T Sym. I th. M2
8131
BAL. I LIMIT M3
8132
BAL. FACT. I M3
8133A
T Sym. I th. M3
8141
BAL. I LIMIT M4
8142
BAL. FACT. I M4
8143A
T Sym. I th. M4
8151
BAL. I LIMIT M5
8152
BAL. FACT. I M5
8153A
T Sym. I th. M5
8161
BALANCE U-LIMIT
8162
BAL. FACTOR U
8163A
T BAL. U LIMIT
8201
TRIP Cir. SUP.
8401
BROKEN WIRE
8403
FUSE FAIL MON.
8422A
FFM I< M1
8423A
FFM I< M2
8424A
FFM I< M3
8426A
FFM U<max (3ph)
8601
EXTERN TRIP 1
7UT613/63x Manual
C53000-G1176-C160-2
Function
C
Min/Max meter
0 .. 1439 min
Min/Max meter
1 .. 365 Days
Min/Max meter
1 .. 365 Days
Measurem.Superv
ON
OFF
Measurem.Superv
ON
OFF
Measurem.Superv
ON
OFF
Measurem.Superv
ON
OFF
Measurem.Superv
ON
OFF
Measurem.Superv
1A
0.10 .. 1.00 A
5A
0.50 .. 5.00 A
Measurem.Superv
0.10 .. 0.90
Measurem.Superv
5 .. 100 sec
Measurem.Superv
1A
0.10 .. 1.00 A
5A
0.50 .. 5.00 A
Measurem.Superv
0.10 .. 0.90
Measurem.Superv
5 .. 100 sec
Measurem.Superv
1A
0.10 .. 1.00 A
5A
0.50 .. 5.00 A
Measurem.Superv
0.10 .. 0.90
Measurem.Superv
5 .. 100 sec
Measurem.Superv
1A
0.10 .. 1.00 A
5A
0.50 .. 5.00 A
Measurem.Superv
0.10 .. 0.90
Measurem.Superv
5 .. 100 sec
Measurem.Superv
1A
0.10 .. 1.00 A
5A
0.50 .. 5.00 A
Measurem.Superv
0.10 .. 0.90
Measurem.Superv
5 .. 100 sec
Measurem.Superv
10 .. 100 V
Measurem.Superv
0.58 .. 0.90
Measurem.Superv
5 .. 100 sec
TripCirc.Superv
ON
OFF
Supervision
OFF
ON
Supervision
OFF
ON
Supervision
1A
0.04 .. 2.00 A
5A
0.20 .. 10.00 A
Supervision
1A
0.04 .. 2.00 A
5A
0.20 .. 10.00 A
Supervision
1A
0.04 .. 2.00 A
5A
0.20 .. 10.00 A
Supervision
2 .. 100 V
External Trips
OFF
ON
Block relay
Setting Options
Default Setting
0 min
7 Days
1 Days
OFF
OFF
OFF
OFF
OFF
0.50 A
2.50 A
0.50
5 sec
0.50 A
2.50 A
0.50
5 sec
0.50 A
2.50 A
0.50
5 sec
0.50 A
2.50 A
0.50
5 sec
0.50 A
2.50 A
0.50
5 sec
50 V
0.75
5 sec
OFF
OFF
OFF
0.10 A
0.50 A
0.10 A
0.50 A
0.10 A
0.50 A
5 V
OFF
A.8 Settings
Comments
MinMax Reset Timer
MinMax Reset Cycle Period
MinMax Start Reset Cycle in
Current Balance Supervision
Voltage Balance Supervision
Voltage Summation Supervision
Current Phase Rotation Supervi-
sion
Voltage Phase Rotation Supervi-
sion
Current Balance Monitor Meas.
Loc. 1
Bal. Factor for Curr. Monitor
Meas.Loc.1
Symmetry Iph: Pick-up delay
Current Balance Monitor Meas.
Loc. 2
Bal. Factor for Curr. Monitor
Meas.Loc.2
Symmetry Iph: Pick-up delay
Current Balance Monitor Meas.
Loc. 3
Bal. Factor for Curr. Monitor
Meas.Loc.3
Symmetry Iph: Pick-up delay
Current Balance Monitor Meas.
Loc. 4
Bal. Factor for Curr. Monitor
Meas.Loc.4
Symmetry Iph: Pick-up delay
Current Balance Monitor Meas.
Loc. 5
Bal. Factor for Curr. Monitor
Meas.Loc.5
Symmetry Iph: Pick-up delay
Voltage Threshold for Balance
Monitoring
Balance Factor for Voltage
Monitor
T Balance Factor for Voltage
Monitor
TRIP Circuit Supervision
Fast broken current-wire supervi-
sion
Fuse Failure Monitor
I< for FFM detection M1
I< for FFM detection M2
I< for FFM detection M3
Maximum Voltage Threshold U<
(3phase)
External Trip Function 1
577