Additional Interface (optional)
Time Synchronisation Interface
7UT613/63x Manual
C53000-G1176-C160-2
Ethernet optical (EN 100)
for IEC 61850 and DIGSI
RS485
FOC
acc. to
ordered version
RS485
Optical fibre (FO)
Time Synchronisation
Connection for flush-mounted
housing
for surface-mounting case
FOC connector type
Connection for flush-mounted
housing
for surface-mounting case
optical wavelength
Transmission speed
Laser class 1 according to
EN 60825-1/-2
permissible optical signal atten-
uation
bridgeable distance
isolated interface for connection of an RTD-box
Connection for flush mounted
case
Connection for surface
mounted case
Test voltage
Transmission speed
Maximum bridgeable
distance
FO connector type
Connection for flush mounted
case
Connection for surface
mounted case
Optical wavelength
Laser class 1 according to EN
60825-1/-2
Permissible optical signal at-
tenuation
Maximum bridgeable
distance
Character idle state
DCF 77 / IRIG B Signal
(telegram format IRIG-B000)
Rear panel, mounting location „A";
9-pin DSUB port
at two-tier terminals on the case bottom
4.1 General
ST–connector transmitter/re-
ceiver
Rear panel, mounting location
"B"
not available
λ = 1350 nm
100 MBit/s
Using
glass fibre 50/125 µm
or using
glass fibre 62.5/125 µm
max. 5 dB, with glass fibre
62.5/125 µm
max. 800 m (0.94 miles)
Rear panel, mounting location
„C",
9-pole DSUB port
in the inclined housing on the
case bottom
500 V; 50 Hz
9,600 Bd
1,000 m (3300 ft)
ST connector
Rear panel, mounting location
„B"
in the inclined housing on the
case bottom
λ = 820 nm
Using glass fibre 50/125 µm or
using glass fibre 62.5/125 µm
max. 8 dB using glass fibre
62.5/125 µm
1,500 m
Selectable: factory setting
„Light off"