Siemens SIPROTEC 7UT613 series Manual page 382

Differential protection
Hide thumbs Also See for SIPROTEC 7UT613 series:
Table of Contents

Advertisement

3 Mounting and Commissioning
Changing the Oper-
ating State
Test in Indication
Direction
Exiting the Test
Mode
Test in Command
Direction
382
Figure 3-23
System interface test with dialog box: Generating indications – Example
On clicking one of the buttons in the column Action you will be prompted for the pass-
word No. 6 (for hardware test menus). After correct entry of the password, individual
annunciations can be initiated. To do so, click on the button Send in the corresponding
line. The corresponding message is issued and can be read out either from the event
log of the SIPROTEC 4 device or from the substation control center.
Further tests remain enabled until the dialog box is closed.
For all information that is transmitted to the central station, test in Setpoint the desired
options in the list which appears:
• Make sure that each checking process is carried out carefully without causing any
danger (see above and refer to DANGER!)
• Click Send in the function to be tested and check whether the corresponding infor-
mation reaches the control center and possibly shows the expected effect. Data
which are normally linked via binary inputs (first character „>") are likewise indicated
to the control center with this procedure. The function of the binary inputs itself is
tested separately.
To end the System Interface Test, click on Close. The dialog box closes. The proces-
sor system is restarted, then the device is ready for operation.
Data which are normally linked via binary inputs (first character „>") are likewise
checked with this procedure. The information transmitted in command direction must
be indicated by the central station. Check whether the reaction is correct.
7UT613/63x Manual
C53000-G1176-C160-2