3 Mounting and Commissioning
Table 3-24
Indications on inconsistencies
Message
„Error1A/5Awrong"
„Err. IN CT M1"
30097
to
„Err. IN CT M5"
30101
„Err.IN CT1..3"
30102
to
„Err.IN CT10..12"
30105
„Err. IN CT IX1"
30106
to
„Err. IN CT IX4"
30109
„FaultConfig/Set"
„GenErrGroupConn"
„GenErrEarthCT"
„GenErrSidesMeas"
„par too low:"
30067
„par too high:"
30068
„settingFault:"
30069
„Diff Adap.fact."
5620
„Diff err. Set."
5623
REF not avail.
5835
REF Adap.fact.
5836
REF Err CTstar
5830
„REF err. Set."
199.2493 Earth fault differential protection setting not plausible
„REF2 Not avail."
205.2491 Restricted earth fault protection 2 is not available for the configured
„REF2 Adap.fact."
205.2494 The matching factor of the current transformers for restricted earth
„REF2 Err CTstar"
205.2492 There is no single-phase measuring input assigned to the starpoint
„REF2 err. Set."
205.2493 Earth fault differential protection setting not plausible
O/C Ph. not active
1860
„O/C Para error"
023.2493 Settings for time overcurrent protection for phase currents not plausi-
„O/C Ph2 Not av."
207.2491 Time overcurrent protection for phase currents 2 is not available for
„O/C Ph2 err Set"
207.2493 Settings for time overcurrent protection for phase currents 2 not plau-
386
No
192
Setting of the rated secondary currents on input/output board incon-
sistent, general
Setting of the rated secondary currents inconsistent for the indicated
to
measured current input (3-phase inputs)
Setting of the rated secondary currents inconsistent for the indicated
to
measured current input (inputs for single-phase busbar protection)
Setting of the rated secondary currents inconsistent for the indicated
to
measured current input (single-phase inputs)
311
Group indication for configuration error
312
General: Error in transformer connection group
313
Error in single-phase inputs for earth fault differential protection
314
Error in assignment of sides and/or measuring locations
Parameter setting value too small for the indicated address number
Parameter setting value too high for the indicated address number
Parameter setting implausible for the indicated address number
The matching factor of the current transformers for the differential
protection is too great or too small
Differential protection setting not plausible
Restricted earth fault protection is not available for the configured
protected object
The matching factor of the current transformers for restricted earth
fault protection is too great or too small.
There is no single-phase measuring input assigned to the starpoint
current for restricted earth fault protection
protected object
fault protection 2 is too great or too small.
current for restricted earth fault protection 2
Time overcurrent protection for phase currents is not available for the
configured protected object
ble
the configured protected object
sible
Meaning
see
Section
2.1.4
3.1.2 („Switch ele-
ments on printed
circuit boards")
2.1.4
3.1.2 („Switch ele-
ments on printed
circuit boards")
2.1.4
3.1.2 („Switch ele-
ments on printed
circuit boards")
2.1.4
3.1.2 („Switch ele-
ments on printed
circuit boards")
2.1.4
2.1.4
2.1.4
2.1.4
2.2
2.2
2.1.4
2.1.4
2.3
2.1.4
2.2
2.1.1
2.4.1
2.4.1
2.3
2.4.1
2.2
2.1.1
2.1.4
2.4.2
2.1.42.1.6
2.4.2
7UT613/63x Manual
C53000-G1176-C160-2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents