Siemens SIPROTEC 7UT613 series Manual page 565

Differential protection
Hide thumbs Also See for SIPROTEC 7UT613 series:
Table of Contents

Advertisement

Addr.
Parameter
1301
REF PROT.
1311
I-REF>
1312A
T I-REF>
1313A
SLOPE
1401
REF PROT.
1411
I-REF>
1412A
T I-REF>
1413A
SLOPE
1701
COLDLOAD PICKUP
1702
Start CLP Phase
1703
Start CLP 3I0
1704
Start CLP Earth
1705
Start CLP Ph 2
1706
Start CLP Ph 3
1707
Start CLP 3I0 2
1708
Start CLP 3I0 3
1709
Start CLP E 2
1711
CB Open Time
1712
Active Time
1713
Stop Time
2001
PHASE O/C
2002
InRushRest. Ph
2008A
MANUAL CLOSE
2011
I>>
2012
I>>
2013
T I>>
2014
I>
2015
I>
2016
T I>
2021
Ip
2022
Ip
2023
T Ip
2024
D Ip
2025
TOC DROP-OUT
2026
IEC CURVE
7UT613/63x Manual
C53000-G1176-C160-2
Function
C
REF
OFF
ON
Block relay
REF
0.05 .. 2.00 I/InS
0.00 .. 60.00 sec; ∞
REF
REF
0.00 .. 0.95
REF 2
OFF
ON
Block relay
REF 2
0.05 .. 2.00 I/InS
0.00 .. 60.00 sec; ∞
REF 2
REF 2
0.00 .. 0.95
ColdLoadPickup
OFF
ON
ColdLoadPickup
No Current
Breaker Contact
ColdLoadPickup
No Current
Breaker Contact
ColdLoadPickup
No Current
Breaker Contact
ColdLoadPickup
No Current
Breaker Contact
ColdLoadPickup
No Current
Breaker Contact
ColdLoadPickup
No Current
Breaker Contact
ColdLoadPickup
No Current
Breaker Contact
ColdLoadPickup
No Current
Breaker Contact
ColdLoadPickup
0 .. 21600 sec
ColdLoadPickup
1 .. 21600 sec
1 .. 600 sec; ∞
ColdLoadPickup
Phase O/C
ON
OFF
Block relay
Phase O/C
ON
OFF
Phase O/C
I>> instant.
I> instant.
Ip instant.
Inactive
0.10 .. 35.00 A; ∞
Phase O/C
1A
0.50 .. 175.00 A; ∞
5A
0.10 .. 35.00 I/InS; ∞
Phase O/C
0.00 .. 60.00 sec; ∞
Phase O/C
0.10 .. 35.00 A; ∞
Phase O/C
1A
0.50 .. 175.00 A; ∞
5A
0.10 .. 35.00 I/InS; ∞
Phase O/C
0.00 .. 60.00 sec; ∞
Phase O/C
Phase O/C
1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
Phase O/C
0.10 .. 4.00 I/InS
0.05 .. 3.20 sec; ∞
Phase O/C
0.50 .. 15.00 ; ∞
Phase O/C
Phase O/C
Instantaneous
Disk Emulation
Phase O/C
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Setting Options
Default Setting
OFF
0.15 I/InS
0.00 sec
0.00
OFF
0.15 I/InS
0.00 sec
0.00
OFF
No Current
No Current
No Current
No Current
No Current
No Current
No Current
No Current
3600 sec
3600 sec
600 sec
OFF
OFF
I>> instant.
4.00 A
20.00 A
4.00 I/InS
0.10 sec
2.00 A
10.00 A
2.00 I/InS
0.30 sec
2.00 A
10.00 A
2.00 I/InS
0.50 sec
5.00
Disk Emulation
Normal Inverse
A.8 Settings
Comments
Restricted Earth Fault Protection
Pick up value I REF>
T I-REF> Time Delay
Slope of Charac. I-REF> = f(I-
SUM)
Restricted Earth Fault Protection
Pick up value I REF>
T I-REF> Time Delay
Slope of Charac. I-REF> = f(I-
SUM)
Cold-Load-Pickup Function
Start Condition CLP for O/C
Phase
Start Condition CLP for O/C 3I0
Start Condition CLP for O/C
Earth
Start Condition CLP for O/C
Phase 2
Start Condition CLP for O/C
Phase 3
Start Condition CLP for O/C 3I0 2
Start Condition CLP for O/C 3I0 3
Start Condition CLP for O/C
Earth 2
Circuit Breaker OPEN Time
Active Time
Stop Time
Phase Time Overcurrent
InRush Restrained O/C Phase
O/C Manual Close Mode
I>> Pickup
I>> Pickup
T I>> Time Delay
I> Pickup
I> Pickup
T I> Time Delay
Ip Pickup
Ip Pickup
T Ip Time Dial
D Ip Time Dial
TOC Drop-out characteristic
IEC Curve
565