Siemens SIPROTEC 7UT613 series Manual page 554

Differential protection
Hide thumbs Also See for SIPROTEC 7UT613 series:
Table of Contents

Advertisement

A Appendix
Addr.
Parameter
0
Pick-up thresh.
0
P.U. THRESHOLD
0
T TRIP DELAY
0A
T PICKUP DELAY
0A
T DROPOUT DELAY
0A
BLOCKED BY FFM
0A
Blk I brkn cond
0A
DROPOUT RATIO
0A
DROPOUT RATIO
0
Function
0
Input Meas. Val
0
Reset Meas. Val
201
FltDisp.LED/LCD
202
Spont. FltDisp.
204
Start image DD
211
No Conn.MeasLoc
212
No AssigMeasLoc
213
NUMBER OF SIDES
216
NUMBER OF ENDS
220
ASSIGNM. 2M,2S
221
ASSIGNM. 3M,2S
222
ASSIGNM. 3M,3S
223
ASSIGNM. 4M,2S
224
ASSIGNM. 4M,3S
225
ASSIGNM. 4M,4S
554
Function
C
Flx
0.01 .. 17.00 Q/SnS
Flx
-0.99 .. 0.99
Flx
0.00 .. 3600.00 sec
Flx
0.00 .. 60.00 sec
Flx
0.00 .. 60.00 sec
Flx
YES
NO
Flx
YES
NO
Flx
0.70 .. 0.99
Flx
1.01 .. 3.00
addMV
MinMax
Dmd
Min/Max/Dmd
Dmd+MiMaD
MiMa/Dmd+MiMaD
addMV
(Setting options depend
on configuration)
addMV
(Setting options depend
on configuration)
Device
Target on PU
Target on TRIP
Device
NO
YES
Device
image 1
image 2
image 3
image 4
image 5
image 6
image 7
P.System Data 1
2
3
4
5
P.System Data 1
2
3
4
5
P.System Data 1
2
3
4
5
P.System Data 1
3
4
5
6
7
8
9
10
11
12
P.System Data 1
M1,M2
P.System Data 1
M1+M2,M3
M1,M2+M3
P.System Data 1
M1,M2,M3
P.System Data 1
M1+M2,M3+M4
M1+M2+M3,M4
M1,M2+M3+M4
P.System Data 1
M1+M2,M3,M4
M1,M2+M3,M4
M1,M2,M3+M4
P.System Data 1
M1,M2,M3,M4
Setting Options
Default Setting
1.10 Q/SnS
0.50
1.00 sec
0.00 sec
0.00 sec
YES
YES
0.95
1.05
MinMax
None
>Reset MinMax
Target on PU
NO
image 1
3
3
3
6
M1,M2
M1+M2,M3
M1,M2,M3
M1+M2,M3+M4
M1+M2,M3,M4
M1,M2,M3,M4
Comments
Pick-up threshold Q-side
Pickup Threshold
Trip Time Delay
Pickup Time Delay
Dropout Time Delay
Block in case of Meas.-Voltage
Loss
Block for broken conductor in CT
path
Dropout Ratio
Dropout Ratio
Scope of the extended measur-
ing values
Input measured value
Reset of ext. meas. values in
progress
Fault Display on LED / LCD
Spontaneous display of flt.an-
nunciations
Start image Default Display
Number of connected Measuring
Locations
Number of assigned Measuring
Locations
Number of Sides
Number of Ends for 1 Phase
Busbar
Assignment at 2 as-
sig.Meas.Loc./ 2 Sides
Assignment at 3 as-
sig.Meas.Loc./ 2 Sides
Assignment at 3 as-
sig.Meas.Loc./ 3 Sides
Assignment at 4 as-
sig.Meas.Loc./ 2 Sides
Assignment at 4 as-
sig.Meas.Loc./ 3 Sides
Assignment at 4 as-
sig.Meas.Loc./ 4 Sides
7UT613/63x Manual
C53000-G1176-C160-2