15 Troubleshooting

Error Descriptions

Event name
Communications Controller Failure
Meaning
A hardware error was detected in the communications controller of the built-in EtherNet/IP port.
Source
EtherNet/IP Function Module
Error attributes
Level
Effects
User program
Indicators
EtherNet/IP NET RUN
OFF
System-defined
Variable
variables
_EIP_LanHwErr
Cause and
Assumed cause
correction
Communications Controller hardware
error
Attached
None
information
Precautions/
After the _EIP_LanHwErr system-defined variable changes to TRUE, it will not change to FALSE unless the power
Remarks
supply to the Controller is cycled.
Event name
MAC Address Error
Meaning
The MAC address in non-volatile memory was not read correctly.
Source
EtherNet/IP Function Module
Error attributes
Level
Effects
User program
Indicators
EtherNet/IP NET RUN
OFF
System-defined
Variable
variables
_EIP_MacAdrErr
Cause and
Assumed cause
correction
Non-volatile memory failure
Attached
None
information
Precautions/
After the _EIP_MacAdrErr system-defined variable changes to TRUE, it will not change to FALSE unless the power
Remarks
supply to the Controller is cycled.
15-20
Source details
Partial fault
Recovery
Continues.
Operation
EtherNet/IP NET ERR
Lights.
Data type
BOOL
Correction
Replace the CPU Unit.
Source details
Partial fault
Recovery
Continues.
Operation
EtherNet/IP NET ERR
Lights.
Data type
BOOL
Correction
Replace the CPU Unit.
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User's Manual (W506)
Event code
04200000 hex
Communications
Detection
port
timing
Cycle the power
Log category
supply.
EtherNet/IP communications will not operate.
EtherNet/IP LINK/ACT
---
Name
Communications Controller Error
Prevention
None
Event code
14200000 hex
Communications
Detection
port
timing
Cycle the power
Log category
supply.
EtherNet/IP communications will not operate.
EtherNet/IP LINK/ACT
---
Name
MAC Address Error
Prevention
None
Continuously
System
At power ON or
Controller reset
System

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac nx-seriesSysmac nx1p2-10 seriesSysmac nx1p2-90 seriesSysmac nj501-5 seriesSysmac nj501-4 seriesSysmac nj501-3 series ... Show all

Table of Contents