Variable name
_EIP_TDLinkStopCmd
Meaning
Tag Data Link Communications Stop Switch
Function
NX-series CPU Units: Change this variable to TRUE to stop tag data links for CIP communications 1.
It automatically changes back to FALSE after tag data link operation stops.
NJ-series CPU Units: Change this variable to TRUE to stop tag data links.
It automatically changes back to FALSE after tag data link operation stops.
Note Do not force this switch to change to FALSE from the user program or from the Sysmac Studio. It changes to
FALSE automatically.
Data type
BOOL
R/W access
R/W
Usage in user pro-
Possible.
gram
Variable name
_EIP1_TDLinkStopCmd
Meaning
CIP Communications1 Tag Data Link Communi-
cations Stop Switch
Function
Change this variable to TRUE to stop tag data links for CIP communications 1.
It automatically changes back to FALSE after tag data link operation stops.
Note Do not force this switch to change to FALSE from the user program or from the Sysmac Studio. It changes to
FALSE automatically.
Note You can use this system-defined variable only for NX-series CPU Units.
Data type
BOOL
R/W access
R/W
Usage in user pro-
Possible.
gram
Variable name
_EIP2_TDLinkStopCmd
Meaning
CIP Communications2 Tag Data Link Communi-
cations Stop Switch
Function
Change this variable to TRUE to stop tag data links for CIP communications 2.
It automatically changes back to FALSE after tag data link operation stops.
Note Do not force this switch to change to FALSE from the user program or from the Sysmac Studio. It changes to
FALSE automatically.
Note You can use this system-defined variable only for the NX701 CPU Units.
Data type
BOOL
R/W access
R/W
Usage in user pro-
Possible.
gram
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User's Manual (W506)
3 System-defined Variables Related to the Built-in EtherNet/IP Port
Retained
Not retained.
Related
---
instructions
Retained
Not retained.
Related
---
instructions
Retained
Not retained.
Related
---
instructions
Global/local
Global
Range of values
TRUE or FALSE
Network Publish
Published.
Global/local
Global
Range of values
TRUE or FALSE
Network Publish
Published.
Global/local
Global
Range of values
TRUE or FALSE
Network Publish
Published.