Omron Sysmac NJ-series User Manual page 102

Machine automation controller cpu unit built-in ethernet/iptm port
Hide thumbs Also See for Sysmac NJ-series:
Table of Contents

Advertisement

3 System-defined Variables Related to the Built-in EtherNet/IP Port
Variable name
_EIP_CipErr
Meaning
CIP Communications Error
Function
This is the error status variable for CIP communications.
NX-series CPU Units: Represents the collective status of the following error flags.
• _EIP1_IdentityErr (CIP Communications1 Identity Error)
• _EIP1_TDLinkCfgErr (CIP Communications1 Tag Data Link Setting Error)
• _EIP1_TDLinkOpnErr (CIP Communications1 Tag Data Link Connection Failed)
• _EIP1_TDLinkErr (CIP Communications1 Tag Data Link Communications Error)
• _EIP1_TagAdrErr (CIP Communications1 Tag Name Resolution Error)
• _EIP1_MultiSwONErr (CIP Communications1 Multiple Switches ON Error)
NJ-series CPU Units: Represents the collective status of the following error flags.
• _EIP_IdentityErr (Identity Error)
• _EIP_TDLinkCfgErr (Tag Data Link Setting Error)
• _EIP_TDLinkOpnErr (Tag Data Link Connection Failed)
• _EIP_TDLinkErr (Tag Data Link Communications Error)
• _EIP_TagAdrErr (Tag Name Resolution Error)
• _EIP_MultiSwOnErr (Multiple Switches ON Error)
Note If a Tag Name Resolution Error occurs, it is recorded in the event log and this variable changes to TRUE.
Data type
WORD
R/W access
R
Usage in user program
Possible.
Variable name
_EIP1_CipErr
Meaning
CIP Communications1 Error
Function
This is the error status variable for CIP communications 1.
It represents the collective status of the following error flags.
• _EIP1_IdentityErr (CIP Communications1 Identity Error)
• _EIP1_TDLinkCfgErr (CIP Communications1 Tag Data Link Setting Error)
• _EIP1_TDLinkOpnErr (CIP Communications1 Tag Data Link Connection Failed)
• _EIP1_TDLinkErr (CIP Communications1 Tag Data Link Communications Error)
• _EIP1_TagAdrErr (CIP Communications1 Tag Name Resolution Error)
• _EIP1_MultiSwONErr (CIP Communications1 Multiple Switches ON Error)
Note If a Tag Name Resolution Error occurs, it is recorded in the event log and this variable changes to TRUE.
Note You can use this system-defined variable only for NX-series CPU Units.
Data type
WORD
R/W access
R
Usage in user program
Possible.
3-36
Refer to Meanings of Error Status Bits for the meanings of the error status bits.
Retained
Related instruc-
tions
Refer to Meanings of Error Status Bits for the meanings of the error status bits.
Retained
Related instruc-
tions
Global/local
Range of values
Not retained.
Network Publish
You can access this variable from the user program with the following
instruction.
• GetEIPError
Global/local
Range of values
Not retained.
Network Publish
You can access this variable from the user program with the following
instruction.
• GetEIPError
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User's Manual (W506)
Global
16#0000 to 16#00F0
Published.
Global
16#0000 to 16#00F0
Published.