Event name
Identity Error
Meaning
The CIP identity information in non-volatile memory was not read correctly.
Source
EtherNet/IP Function Module
Error attributes
Level
Effects
User program
Indicators
EtherNet/IP NET RUN
---
System-defined
Variable
variables
_EIP_IdentityErr
_EIP1_IdentityErr
_EIP2_IdentityErr
Cause and
Assumed cause
correction
Non-volatile memory failure
Attached
None
information
Precautions/
None
Remarks
*1 This applies to an NJ-series CPU Unit.
*2 This applies to an NX-series CPU Unit.
Event name
MAC Address Error
Meaning
The MAC address in non-volatile memory was not read correctly.
Source
EtherNet/IP Function Module
Error attributes
Level
Effects
User program
Indicators
EtherNet/IP NET RUN
OFF
System-defined
Variable
variables
_EIP1_MacAdrErr
_EIP2_MacAdrErr
Cause and
Assumed cause
correction
Non-volatile memory failure
Attached
None
information
Precautions/
After the _EIP1_MacAdrErr or _EIP2_MacAdrErr system-defined variable changes to TRUE, it will not change to
Remarks
FALSE unless the power supply to the Controller is cycled.
* This event code occurs for unit version 1.10 or later of the CPU Unit.
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User's Manual (W506)
Source details
Minor fault
Recovery
Continues.
Operation
EtherNet/IP NET ERR
Lights.
Data type
*1
BOOL
*2
BOOL
BOOL
*2
Correction
Replace the CPU Unit.
Source details
Minor fault
Recovery
Continues.
Operation
EtherNet/IP NET ERR
Lights.
Data type
BOOL
BOOL
Correction
Replace the CPU Unit.
15 Troubleshooting
Event code
14210000 hex
*1
*2
Detection
CIP,
CIP1,
or
timing
*2
CIP2
Cycle the power
Log category
supply.
EtherNet/IP communications are not possible for the rele-
vant communications port.
EtherNet/IP LINK/ACT
---
Name
Identify Error
CIP Communications1 Identity Error
CIP Communications2 Identity Error
Prevention
None
Event code
14230000 hex*
Communications
Detection
port 1 or 2
timing
Cycle the power
Log category
supply.
EtherNet/IP communications are not possible for the rele-
vant communications port.
EtherNet/IP LINK/ACT
---
Name
Port1 MAC Address Error
Port2 MAC Address Error
Prevention
None
At power ON or
Controller reset
System
15
At power ON or
Controller reset
System
15-25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac nx-seriesSysmac nx1p2-10 seriesSysmac nx1p2-90 seriesSysmac nj501-5 seriesSysmac nj501-4 seriesSysmac nj501-3 series ... Show all

Table of Contents