(3) Status Details of the Built-in EtherNet/IP Port
Bit
Name
0
Owned
1
Reserved
2
Configured
3
Reserved
4 to 7
Extended Device Status
8
Minor Recoverable Fault
9
Minor Unrecoverable Fault
10
Major Recoverable Fault
11
Major Unrecoverable Fault
12 to 15
Reserved
Request Paths (IOIs) to Specify Objects
When you specify an object, specify the request path (IOI) for each service code as given below.
Service code
01 hex
Get_Attribute_All
0E hex
Get_Attribute_Single
05 hex
Reset
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User's Manual (W506)
Indicates when the built-in EtherNet/IP port has an open connection as the
target of a tag data link.
Always FALSE.
Tag data link settings exist.
Always FALSE.
Indicates the status of the built-in EtherNet/IP port.
b7
b6
b5
0
1
0
0
0
1
0
0
1
0
1
1
0
1
1
TRUE when any of the following errors occurs.
• IP Route Table Setting Error
• DNS Server Connection Failed
• Tag Data Link Setting Error
• Tag Data Link Timeout
• Tag Data Link Connection Timeout
• FTP Server Setting Error
• NTP Client Setting Error
• SNMP Setting Error
• NTP Server Connection Failed
• Tag Name Resolution Error
TRUE when the following error occurs.
• Identity Error
TRUE when any of the following errors occurs.
• IP Address Duplication Error
• BOOTP Server Connection Error
• Basic Ethernet Setting Error
• IP Address Setting Error
TRUE when any of the following errors occurs.
• Communications Controller Failure
• MAC Address Error
Always FALSE.
Class ID
Instance ID
01 hex
• Specifying a service for a class: 00 hex
• Specifying a service for an instance:
Always 01 hex
Always 01 hex
8 CIP Message Communications
Description
b4
1 A major fault occurred.
0 A timeout occurred in one or more target con-
nections.
1 Indicates that there are no tag data link settings.
0 Indicates that one or more connections are per-
forming communications normally.
1 Other than the above.
Not required.
• Reading a class attribute: 01 or 02
hex
• Reading an instance attribute: 01 to
07 hex
Not required.
8
Attribute ID
8-49