Omron Sysmac NJ-series User Manual page 471

Machine automation controller cpu unit built-in ethernet/iptm port
Hide thumbs Also See for Sysmac NJ-series:
Table of Contents

Advertisement

Event name
IP Address Setting Error
Meaning
An error was detected in the IP address settings.
Source
EtherNet/IP Function Module
Error attributes
Level
Effects
User program
Indicators
EtherNet/IP NET RUN
OFF
System-defined
Variable
variables
_EIP1_IPAdrCfgErr
_EIP2_IPAdrCfgErr
Cause and
Assumed cause
correction
Parameter error
Power was interrupted when a down-
load was in progress for the built-in
EtherNet/IP port settings.
The IP address acquired from
BOOTP server is illegal.
A memory error occurred.
Attached
Attached information 1: Type of errors (01 hex: Non-volatile memory access error, 02 hex: Inconsistency in settings)
information
Attached information 2: Error details (00 hex: Non-volatile memory access error)
When the settings are inconsistent
(11 hex: Illegal IP address, 12 hex: Illegal subnet mask)
Precautions/
The cause of error can be identified with the attached information.
Remarks
* This event code occurs for unit version 1.10 or later of the CPU Unit.
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User's Manual (W506)
Source details
Minor fault
Recovery
Continues.
Operation
EtherNet/IP NET ERR
Flashes at 1-s intervals.
Data type
BOOL
BOOL
Correction
Identify the error from the attached
information, correct the setting, and
then download the settings again.
Perform the Clear All Memory opera-
tion or download the settings again.
Correct the IP address that was pro-
vided to this port by the BOOTP
server so that it is within the range
specified for an NX-series Controller.
If operation is not recovered by the
above, replace the CPU Unit.
15 Troubleshooting
Event code
34290000 hex*
Communications
Detection
port 1 or 2
timing
Automatic recov-
Log category
ery (after down-
loading the
settings), cycle
the power sup-
ply, or reset Con-
troller.
EtherNet/IP communications are not possible for the rele-
vant communications port.
EtherNet/IP LINK/ACT
---
Name
Port1 IP Address Setting Error
Port2 IP Address Setting Error
Prevention
None
Do not turn OFF the power supply to
the Controller while a download is in
progress for the built-in EtherNet/IP
port settings.
Correct the IP address that was pro-
vided to this port by the BOOTP
server so that it is within the range
specified for an NX-series Controller.
None
At power ON or
Controller reset
System
15
15-33

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac nx-seriesSysmac nx1p2-10 seriesSysmac nx1p2-90 seriesSysmac nj501-5 seriesSysmac nj501-4 seriesSysmac nj501-3 series ... Show all

Table of Contents