15 Troubleshooting
Event name
IP Address Setting Error
Meaning
An error was detected in the IP address settings.
Source
EtherNet/IP Function Module
Error attributes
Level
Effects
User program
Indicators
EtherNet/IP NET RUN
OFF
System-defined
Variable
variables
_EIP_IPAdrCfgErr
Cause and
Assumed cause
correction
Setting error
Power was interrupted when a down-
load was in progress for the built-in
EtherNet/IP port settings.
The IP address acquired from
BOOTP server is illegal.
Memory error
Attached
Attached information 1: Type of errors (01 hex: Non-volatile memory access error, 02 hex: Inconsistency in settings)
information
Attached information 2: Error details (00 hex: Non-volatile memory access error
When settings are inconsistent (11 hex: Illegal IP address, 12 hex: Illegal subnet mask, 13 hex: Illegal default gateway,
14 hex: Preferred DNS setting error, 15 hex: Alternate DNS setting error, 16 hex: Illegal domain name)
Precautions/
The cause of error can be identified with the attached information.
Remarks
15-22
Source details
Partial fault
Recovery
Continues.
Operation
EtherNet/IP NET ERR
Flashes at 1-s intervals.
Data type
BOOL
Correction
Identify the error from the attached
information, correct the setting, and
then download the settings again.
Perform the Clear All Memory opera-
tion or download the settings again.
Correct the IP address that was pro-
vided to this port by the BOOTP
server so that it is within the range
specified for an NJ-series Controller.
If operation is not recovered by the
above, replace the CPU Unit.
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User's Manual (W506)
Event code
34220000 hex
Communications
Detection
port
timing
Automatic recov-
Log category
ery (after down-
loading the
settings), cycle
the power sup-
ply, or reset Con-
troller
EtherNet/IP communications will not operate.
EtherNet/IP LINK/ACT
---
Name
IP Address Setting Error
Prevention
None
Do not turn OFF the power supply to
the Controller while a download is in
progress for the built-in EtherNet/IP
port settings.
Set the IP address that was provided
to this port by the BOOTP server so
that it is within the range specified for
an NJ-series Controller.
None
At power ON or
Controller reset
System