Omron Sysmac NJ-series User Manual page 459

Machine automation controller cpu unit built-in ethernet/iptm port
Hide thumbs Also See for Sysmac NJ-series:
Table of Contents

Advertisement

Event name
EtherNet/IP Processing Error
Meaning
A fatal error was detected in the EtherNet/IP Function Module.
Source
EtherNet/IP Function Module
Error attributes
Level
Effects
User program
Indicators
EtherNet/IP NET RUN
OFF
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
Hardware has failed.
Attached
None
information
Precautions/
None
Remarks
Event name
Basic Ethernet Setting Error
Meaning
An error was detected in the Ethernet settings.
Source
EtherNet/IP Function Module
Error attributes
Level
Effects
User program
Indicators
EtherNet/IP NET RUN
OFF
System-defined
Variable
variables
_EIP_EtnCfgErr
Cause and
Assumed cause
correction
Setting error
Power was interrupted when a down-
load was in progress for the built-in
EtherNet/IP port settings.
Memory error
Attached
Attached information 1: Type of errors (01 hex: Non-volatile memory access error, 02 hex: Inconsistency in settings)
information
Attached information 2: Error details
(00 hex: Non-volatile memory access error, 11 hex: Incorrect baud rate setting, 12 hex: Unsupported baud rate)
Precautions/
The cause of error can be identified with the attached information.
Remarks
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User's Manual (W506)
Source details
Partial fault
Recovery
Continues.
Operation
EtherNet/IP NET ERR
Lights.
Data type
---
Correction
Replace the CPU Unit.
Source details
Partial fault
Recovery
Continues.
Operation
EtherNet/IP NET ERR
Flashes at 1-s intervals.
Data type
BOOL
Correction
Identify the error from the attached
information, correct the setting, and
then download the settings again.
Perform the Clear All Memory opera-
tion or download the settings.
If operation is not recovered by the
above, replace the CPU Unit.
15 Troubleshooting
Event code
14220000 hex
Communications
Detection
port
timing
Cycle the power
Log category
supply.
EtherNet/IP communications will not operate.
EtherNet/IP LINK/ACT
---
Name
---
Prevention
None
Event code
34210000 hex
Communications
Detection
port
timing
Automatic recov-
Log category
ery, cycle the
power supply, or
reset Controller
EtherNet/IP communications will not operate.
EtherNet/IP LINK/ACT
---
Name
Basic Ethernet Setting Error
Prevention
None
Do not turn OFF the power supply to
the Controller while a download is in
progress for the built-in EtherNet/IP
port settings.
None
Continuously
System
At power ON or
Controller reset
System
15
15-21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac nx-seriesSysmac nx1p2-10 seriesSysmac nx1p2-90 seriesSysmac nj501-5 seriesSysmac nj501-4 seriesSysmac nj501-3 series ... Show all

Table of Contents