CIP message
service:
Explicit mes-
*7
sages
SNMP
EtherNet/IP conformance test
Ethernet interface
*1 If tag data links are being used, use 100Base-TX or 1000Base-T.
*2 Here, pps means "packets per second" and indicates the number of packets that can be processed in one sec-
ond.
*3 If the two built-in EtherNet/IP ports are used simultaneously, the maximum communications data size for two
ports in total will be reached.
*4 To use a data size of 505 bytes or higher, the system must support a large forward open (an optional CIP spec-
ification). The CS, CJ, NJ, and NX-series Units support a large forward open, but before connecting to nodes
of other companies, confirm that those devices also support it.
*5 If the parameters of the built-in EtherNet/IP port are changed, the port is restarted. When other nodes are in
communications with the affected node, the communications will temporarily time out and automatically
recover after the restart.
*6 Because the built-in EtherNet/IP port is equipped with an IGMP client (version 2), unnecessary multicast pack-
ets can be filtered by an Ethernet switch that supports IGMP snooping.
*7 The built-in EtherNet/IP port uses the TCP/UDP port numbers shown in the following table.
Do not set the same port number for more than one TCP/UDP service.
Service
EIP data links
Used by system
CIP messages
FTP client data transfer port
DNS client
BOOTP client
HTTP server
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User's Manual (W506)
NX701-
Item
Unit version 1.10 or
Connections: 128
Class 3 (con-
per port (total of 256
nected)
with two ports) (cli-
ents plus server)
Number of clients that can communicate at one time: 32 max.
UCMM (uncon-
nected)
Number of servers that can communicate at one time: 32 max.
Supported.
CIP routing is supported for the following remote Units: NX701-,
NJ501-, NJ301-, NJ101-, CS1W-EIP21, CJ1W-
*8
CIP routing
EIP21, CJ2H-CPU-EIP, and CJ2M-CPU3.
Using a combination of any Units above, communication can be
extended up to a maximum of 8 levels.
Agents
SNMPv1 or SNMPv2c
MIB
MIB-II
Conforms to CT11
10Base-T, 100Base-
TX, or 1000Base-T
Auto negotiation or
fixed settings
Protocol
UDP
UDP
TCP
TCP
TCP
TCP/UDP
UDP
TCP
Specifications
NX1P2-

Unit version
later
1.13 or later
Number of connections: 32 (clients + servers)
Conforms to
CT13
10Base-T or 100Base-TX
Auto negotiation or fixed settings
Port number
2222
2223, 2224
9610
44818
20
53
68
80
1 Introduction
NJ501-/NJ301-/
NJ101-
Unit version
Unit version
1.00 to 1.02
1.03 or later
Conforms to CT8
Remarks
Fixed values
1
1-9