Variable name
_EIP2_CipErr
Meaning
CIP Communications2 Error
Function
This is the error status variable for CIP communications 2.
It represents the collective status of the following error flags.
• _EIP2_IdentityErr (CIP Communications2 Identity Error)
• _EIP2_TDLinkCfgErr (CIP Communications2 Tag Data Link Setting Error)
• _EIP2_TDLinkOpnErr (CIP Communications2 Tag Data Link Connection Failed)
• _EIP2_TDLinkErr (CIP Communications2 Tag Data Link Communications Error)
• _EIP2_TagAdrErr (CIP Communications2 Tag Name Resolution Error)
• _EIP2_MultiSwONErr (CIP Communications2 Multiple Switches ON Error)
Note If a Tag Name Resolution Error occurs, it is recorded in the event log and this variable changes to TRUE.
Note You can use this system-defined variable only for the NX701 CPU Units.
Data type
WORD
R/W access
R
Usage in user program
Possible.
Variable name
_EIP_TcpAppErr
Meaning
TCP Application Communications Error
Function
This is the error status variable for TCP application communications.
It represents the collective status of the following error flags.
• _EIP_TcpAppCfgErr (TCP Application Setting Error)
• _EIP_NTPSrvErr (NTP Server Connection Error)
Note Refer to Meanings of Error Status Bits for the meanings of the error status bits.
Data type
WORD
R/W access
R
Usage in user program
Possible.
Variable name
_EIP_MacAdrErr
Meaning
MAC Address Error
Function
NX-series CPU Units: Indicates that an error occurred when the MAC address was read on the communications
port 1 at startup.
TRUE: Error
FALSE: Normal
NJ-series CPU Units: Indicates that an error occurred when the MAC address was read at startup.
TRUE: Error
FALSE: Normal
Data type
BOOL
R/W access
R
Usage in user program
Possible.
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User's Manual (W506)
3 System-defined Variables Related to the Built-in EtherNet/IP Port
Refer to Meanings of Error Status Bits for the meanings of the error status bits.
Retained
Not retained.
Related
You can access this variable from the user program with the following instruction.
instructions
• GetEIPError
Retained
Not retained.
Related
You can access this variable from the user program with the following instruction.
instructions
• GetEIPError
Retained
Not retained.
Related
---
instructions
Global/local
Global
Range of values
16#0000 to 16#00F0
Network Publish
Published.
Global/local
Global
Range of values
16#0000 to 16#00F0
Network Publish
Published.
Global/local
Global
Range of values
TRUE or FALSE
Network Publish