For data logging error codes, SM, SD, and troubleshooting by symptom, refer to the following.
User's Manual (Hardware Design, Maintenance and Inspection) for the CPU module used
This chapter provides only the list of the errors that may occur in data logging.
13.1

List of the Errors That May Occur in Data Logging

If an error occurs in data logging, a diagnostic error will not be reported. Instead, the special relay (Data logging error)
turns on and a value indicating the cause of the error is stored in the special register (Data logging error cause).
If the data logging is stopped with an error, the logging can be restarted by using SM1938 (Data logging restart flag (at
logging stop with error)).
For information on "Registration" and "Cancel" in the "Timing of occurrence" column, refer to  Page 63, Section
6.4.
*1
This flag is supported by the QnUDVCPU and QnUDPVCPU with a serial number (first five digits) "17103" or later, or
LCPU modules (except for the L02SCPU and L02SCPU-P) with a serial number (first five digits) "17102" or later.
No.
Writing or registration was attempted to the SD memory card in one of the
following conditions.
• An SD memory card was not installed.
1
• LCPU: An SD memory card was installed but the SD memory card access
control switch was not slid down.
• The SD memory card was disabled by SM606 (SD memory card forced
disable instruction).
2
Writing or registering data logging settings was attempted to a failed memory.
With the SD memory card write-protected, writing or deleting data logging
3
settings was attempted to it.
Although the target memory does not have enough free space, writing data
4
logging settings was attempted.
5
Writing data logging settings to the target memory was not completed.
While the data logging function is in operation (the logging status is
6
"Executing", "Saving the logging data", "Completed", "Pausing", or "Error"),
data logging registration to a different memory was attempted.
While the data logging function is in operation (the logging status is
"Executing", "Saving the logging data", "Completed", "Pausing", or "Error"),
7
writing, deleting, or registering data logging settings was attempted to
Common setting or a data logging setting of a registered setting number.
Writing or deleting data logging settings, or data logging operation was
8
attempted to a file in access.
180
TROUBLESHOOTING
*1
Error cause
Value in special register
Timing of
(Data logging error cause
occurrence
information)
Writing settings
208
Registration
Writing settings
216
Registration
• Writing settings
• Deleting settings
Writing settings
Registration
• Writing settings
• Deleting settings
• Registration
• Writing settings
• Deleting settings
• Registration
• Cancel
Error response
No.
41FE
H
41FE
H
H
4123
H
H
41DF
H
41CF
H
Abnormal memory
access
error other than
No.1 to No.4
4270
H
4271
H
413B
H