Unit Number Switch - Omron CS1W-AD041-V1 Operation Manual

Sysmac cs/cj series
Table of Contents

Advertisement

Components and Switch Settings
2-3-2

Unit Number Switch

Switch
CS1W-AD041-V1/AD081-V1
setting
Unit
Special/O Unit Area
number
addresses
0
Unit #0
CIO 2000 to
CIO 2009
1
Unit #1
CIO 2010 to
CIO 2019
2
Unit #2
CIO 2020 to
CIO 2029
3
Unit #3
CIO 2030 to
CIO 2039
4
Unit #4
CIO 2040 to
CIO 2049
5
Unit #5
CIO 2050 to
CIO 2059
6
Unit #6
CIO 2060 to
CIO 2069
7
Unit #7
CIO 2070 to
CIO 2079
8
Unit #8
CIO 2080 to
CIO 2089
9
Unit #9
CIO 2090 to
CIO 2099
10
Unit #10
CIO 2100 to
CIO 2109
~
~
~
n
Unit #n
CIO 2000 + (n x 10)
to CIO 2000 + (n x
10) + 9
~
~
~
94
Unit #94
CIO 2940 to
CIO 2949
95
Unit #95
CIO 2950 to
CIO 2959
LED
Meaning
ADJ (yellow) Adjusting
ERH (red)
Error in the
CPU Unit
The CPU Unit and Analog Input Unit exchange data via the Special I/O Unit
Area and the Special I/O Unit DM Area. The Special I/O Unit Area and Special
I/O Unit DM Area word addresses that each Analog Input Unit occupies are
set by the unit number switch on the front panel of the Unit.
Always turn OFF the power before setting the unit number. Use a flat-blade
screwdriver, being careful not to damage the slot in the screw. Be sure not to
leave the switch midway between settings.
Special I/O Unit DM
Area addresses
D20000 to D20099
D20100 to D20199
D20200 to D20299
D20300 to D20399
D20400 to D20499
D20500 to D20599
D20600 to D20699
D20700 to D20799
D20800 to D20899
D20900 to D20999
D21000 to D21099
~
D20000 + (n x 100)
to
D20000 + (n x 100) +
99
~
D29400 to D29499
D29500 to D29599
Indicator
Operating status
Flashing
Operating in offset/gain adjustment
mode.
Not lit
Other than the above.
Lit
Error has occurred during data exchange
with the CPU Unit.
Not lit
Operating normally.
CS1W-AD161 (See note 2.)
Unit
Special/O Unit Area
number
addresses
Unit #0
CIO 2000 to
CIO 2019
Unit #1
CIO 2010 to
CIO 2029
Unit #2
CIO 2020 to
CIO 2039
Unit #3
CIO 2030 to
CIO 2049
Unit #4
CIO 2040 to
CIO 2059
Unit #5
CIO 2050 to
CIO 2069
Unit #6
CIO 2060 to
CIO 2079
Unit #7
CIO 2070 to
CIO 2089
Unit #8
CIO 2080 to
CIO 2099
Unit #9
CIO 2090 to
CIO 2109
Unit #10
CIO 2100 to
CIO 2119
~
~
Unit #n
CIO 2000 + (n x 10)
to CIO 2000 + (n x
10) + 19
~
~
Unit #94
CIO 2940 to
CIO 2959
Not
---
used.
Section 2-3
Special I/O Unit DM
Area addresses
D20000 to D20199
D20100 to D20299
D20200 to D20399
D20300 to D20499
D20400 to D20599
D20500 to D20699
D20600 to D20799
D20700 to D20899
D20800 to D20999
D20900 to D21099
D21000 to D21199
~
D20000 + (n x 100)
to
D20000 + (n x 100) +
199
~
D29400 to D29499
---
29

Hide quick links: