Operating Procedure
201904 Input 1 Disconnection Detection Flag (See note c.)
Always ON Flag
201906 Input 3 Disconnection Detection Flag (See note c.)
201907 Input 4 Disconnection Detection Flag (See note c.)
300
b) Set as required.
MOV (021)
MOV (021)
MOV (021)
MOV (021)
c) The input Disconnection Detection Flag is allocated to bits 04 to
07 of word (n + 9). Refer to Allocations for Normal Mode on
page 316 and 7-6-6 Input Disconnection Detection Function for
further details.
2. The following example shows how to use analog outputs.
The setting address D00200 is stored in words (n+1) to (n+2) of the Special I/
O Unit Area (CIO 2011 to CIO 2012) as a signed binary value between 0000
to 0FA0 hex.
• The following table shows the addresses used for analog output.
Output number
Input signal range
1
0 to 10 V
2
4 to 20 mA
Note a) The addresses are set according to the unit number of the Special
I/O Unit. Refer to 7-3-2 Unit Number Switch for further details.
For 1 to 5 V, the hexadecimal value 0000
to 0FA0 will be stored in CIO 2015, so if
there is no disconnection (i.e., 201904 is
2015
OFF), CIO 2015 will be stored in
D00100
D00100.
In the same way, for 0 to 10 V, CIO 2016
will be stored in D00101.
2016
The disconnection detection function is not
valid for the 0 to 10-V range, so the
D00101
Disconnection Detection Flag cannot be
used.
In the same way, for 4 to 20 mA, CIO 2017
will be stored in D00102.
2017
D00102
In the same way, for 4 to 20 mA, CIO 2018
will be stored in D00103.
2018
D00103
Output setting
address
(n = CIO 2010)
See note 1.
(n+1) = CIO 2011
(n+2) = CIO 2012
Section 7-2
Original
conversion
address
D00200
D00201