Obtaining Analog Input Conversion Values
This is a program for obtaining the Analog Input Unit's input conversion values. Individual input values are
obtained by MOV(021) when their Disconnection Detection Flags are OFF.
Unit Settings
Item
Unit
Unit number
Operation mode
Input number
Input signal range
Program Example
Writing Analog Output Set Values
This is a program for writing the Analog Output Unit's output set values.
Unit Settings
Item
Unit
Unit number
Operation mode
Output number
Output signal range
Appendix B

Sample Programs

Setting contents
CS1W-AD081-V1
#0
Normal mode
Inputs 1 to 8 used
All input numbers, 1 to 5 V
Input 1 Disconnection Detection Flag
200900
Input 2 Disconnection Detection Flag
200901
Input 8 Disconnection Detection Flag
200907
Setting contents
CS1W-DA08V
#0
Normal mode
Output 1 used
Output number 1, 0 to 10 V
Actual settings
---
Unit number switch: 00
Back-panel DIP switch: All OFF
D20000 = 00FF
D20001 = AAAA
MOV(021)
Conversion value
2001
D00000
MOV(021)
2002
Conversion value
D00001
MOV(021)
Conversion value
2008
D00007
Actual settings
---
Unit number switch: 00
Back-panel DIP switch: All OFF
D20000 = 0001
D20001 = 0001