Analog Output Functions and Operating Procedures
Writing Set Values
Example 1
Input condition
Example 2
Input condition
198
ON again, or set the Special I/O Unit Restart Bit to ON. The contents of the
data memory settings will be transferred to the Special I/O Unit when the
power is turned ON or the Special I/O Unit Restart Bit is ON.
4. The CJ1W-DA08C provides current output (4 to 20 mA) only. The CJ1W-
DA08C cannot be used for voltage output.
Analog output set values are written to CIO words n+1 to n+8 (CIO words n+1
to n+4 for the CJ1W-DA041, n+1 and n+2 for the CJ1W-DA021
Word
n+1
Output 1 set value
n+2
Output 2 set value
n+3
Output 3 set value
n+4
Output 4 set value
n+5
Output 5 set value
n+6
Output 6 set value
n+7
Output 7 set value
n+8
Output 8 set value
For the CIO word addresses, n = CIO 2000 + (unit number x 10).
Use MOV(021) or XFER(070) to write values in the user program.
In this example, the set value from only one output is written. (The unit num-
ber is 0.)
In this example, multiple set values are written. (The unit number is #0.)
Note If the set value has been written outside the specified range, an output setting
error will occur, and the value set by the output hold function will be output.
Function
16-bit binary data
The set value stored in D 00001
MOV (021)
is written to CIO word 2001 (out-
D00001
put number 1).
2001
XFER(070)
The set values stored in D 00001 to
#0008
D 00008 are written to CIO words
2001 to 2008 (outputs 1 to 8).
D00001
2001
Section 5-6
).
Stored value