Fixed Data Allocations - Omron CS1W-AD041-V1 Operation Manual

Sysmac cs/cj series
Table of Contents

Advertisement

Exchanging Data with the CPU Unit
5-5-4

Fixed Data Allocations

DM Allocation and
Contents
SYSMAC CJ-series PLC
(Special I/O Unit DM Area)
D20000 to D20099
Unit #0
D20100 to D20199
Unit #1
D20200 to D20299
Unit #2
D20300 to D20399
Unit #3
D20400 to D20499
Unit #4
D20500 to D20599
Unit #5
D20600 to D20699
Unit #6
D20700 to D20799
Unit #7
D20800 to D20899
Unit #8
D20900 to D20999
Unit #9
D21000 to D21099
Unit #10
~
D20000 + (n x 100) to
Unit #n
D20000 + (n x 100) + 99
~
D29500 to D29599
Unit #95
Note
DM Allocation Contents
DM word
15
14
D(m)
Not used.
D(m+1)
Not used.
D(m+2)
Not used.
D(m+3)
Not used.
190
The initial settings of the Analog Output Unit are set according to the data
allocated in the Special I/O Unit DM Area. Settings, such as the outputs used,
and the analog output signal ranges must be set in this area.
Word
Data is automatically
transferred to each unit
number when the power
is turned ON, or when
the Special I/O Unit
Restart Bit is turned ON.
~
~
1. The Special I/O Unit DM Area words that are occupied by the Analog Out-
put Unit are set using the unit number switch on the front panel of the Unit.
Refer to 5-3-2 Unit Number Switch for details on the method used to set
the unit number switch.
2. If two or more Special I/O Units are assigned the same unit number, a
"UNIT No. DPL ERR" error (in the Programming Console) will be generat-
ed (A40113 will turn ON) and the PLC will not operate.
The following table shows the allocation of DM words and bits for both normal
and adjustment mode.
CJ1W-DA021
13
12
11
10
CJ1W-DA021/041/08V/08C Analog Output Unit
(Fixed Data Area)
D(m)
D(m+1)
D(m+2 to
m+9)
(See note.)
D(m+10 to
m+17)
D(m+18)
D(m+19 to
m+34)
m = 20000 + (unit number x 100)
Bits
9
8
7
6
Not used.
Not used.
Output 1: Output status when conversion stopped
Output 2: Output status when conversion stopped
Section 5-5
Outputs used
setting
Output signal
range
Output hold
function setting
Not used.
Conversion time/
resolution and
operation mode
settings
Scaling function
setting
5
4
3
2
Output use
setting
Out-
put 2
Output signal range set-
ting
Output 2
Output 1
1
0
Out-
put 1