Internal Circuitry - Omron CS1W-AD041-V1 Operation Manual

Sysmac cs/cj series
Table of Contents

Advertisement

Wiring
CS1W-AD161
CN2 Inputs 9 to16
Input 9+
Current mode 9
Input 9−
AG
Input 11+
Current mode 11
Input 11−
AG
Input 13+
Current mode 13
Input 13−
AG
Input 15+
Current mode 15
Input 15−
AG
NC
Note
!Caution Do not make any connections to the N.C. terminals.
2-4-2

Internal Circuitry

Input Circuitry
1
2
Input 10+
3
4
Current mode 10
5
6
Input 10−
7
8
AG
9
10
Input 12+
11
12
Current mode 12
13
14
Input 12−
16
AG
15
17
18
Input 14+
19
20
Current mode 14
21
22
Input 14−
23
24
AG
25
26
Input 16+
27
28
Current mode 16
29
30
Input 16−
31
32
AG
33
34
NC
1. The analog input numbers that can be used are set in the Data Memory
(DM).
2. The input signal ranges for individual inputs are set in the Data Memory
(DM). They can be set in units of input numbers.
3. The AG terminals (A8, B8) are connected to the 0-V analog circuit in the
Unit. Connecting shielded input lines can improve noise resistance.
The following diagrams show the internal circuitry of the analog input section.
CS1W-AD041-V1/AD081-V1
Input (+)
Input (–)
AG
(analog
0 V)
CN1 Inputs 1 to 8
Input 1+
Current mode 1 3
Input 1−
AG
Input 3+
Current mode 3 11
Input 3−
AG
Input 15+
Current mode 5 19
Input 5−
AG
Input 7+
Current mode 7 27
Input 7−
AG
NC
15 k
250
1 M
15 k
Voltage/
current
input switch
1 M
AG (common to all inputs)
Section 2-4
1
2
Input 2+
4
Current mode 2
5
6
Input 2−
7
8
AG
9
10
Input 4+
12
Current mode 4
13
14
Input 4−
15
16
AG
17
18
Input 6+
20
Current mode 6
21
22
Input 6−
23
24
AG
25
26
Input 8+
28
Current mode 8
29
30
Input 8−
31
32
AG
33
34
NC
15 k
Input circuit
and
conversion
15 k
circuit
33

Hide quick links: