Adjusting Offset and Gain
278
Change the set value, using the Up Bit (bit 03 of word n+1) and the Down
Bit (bit 02 of word n+1).
Bit
15 14
13
12
Word n+1
While the Up Bit is ON, the set value will be
increased by 1 resolution every 0.5 seconds.
After it has been ON for 3 seconds, the set
value will be increased by 1 resolution every
0.1 seconds.
While the Down Bit is ON, the set value will be
decreased by 1 resolution every 0.5 seconds.
After it has been ON for 3 seconds, the set
value will be decreased by 1 resolution every
0.1 seconds.
• The following example increases the output voltage.
C
A
CONT
SHIFT
2
0
#
The bit will remain ON until the output voltage becomes an appropriate val-
ue, at which time, the output will turn OFF.
SET
RESET
• The following example decreases the output voltage.
C
A
CONT
SHIFT
2
0
#
The bit will remain ON until the output voltage becomes an appropriate val-
ue, at which time, the output will turn OFF.
SET
RESET
11
10
09 08
07
06
A
B
A
D
0
1
0
3
200103
200103
200103
A
B
A
C
1
0
2
0
200102
200102
200102
Section 6-9
05
04 03
02
01
00
Up Bit
Down Bit
MON
^ OFF
^ ON
^ OFF
MON
^ OFF
^ ON
^ OFF