Data Memory Coding Sheets
DM word
15
m
m+1
m+2
Input 1: Mean value processing setting
m+3
Input 2: Mean value processing setting
Input 3: Mean value processing setting
m+4
m+5
Input 4: Mean value processing setting
Conversion time/
m+18
resolution setting
Note m=20000+ unit number x 100 is allocated as the DM number.
Setting contents
8
7
0
Input use
designation
Input signal
range setting
Operation mode
setting
Use Designation
03 02
01
0: Do not use.
1: Use
Signal Range Setting
07 06
05
00: −10 to 10 V
01: 0 to 10 V
10: 1 to 5 V / 4 to 20 mA (change using voltage/current switch)
11: 0 to 5 V
Mean Value Processing Setting
15
12 11
3
16
0000: Mean value processing with 2 buffers.
0001: No mean value processing
0002: Mean value processing with 4 buffers.
0003: Mean value processing with 8 buffers.
0004: Mean value processing with 16 buffers.
0005: Mean value processing with 32 buffers.
0006: Mean value processing with 64 buffers.
Conversion Time/Resolution Setting
15
12 11
3
16
00: Conversion time of 1 ms and resolution of 4,000
C1: Conversion time of 250 µs and resolution of 8,000
Operation Mode Setting
07
04 03
1
16
00: Normal mode
C1: Adjustment mode
Appendix C
00
04
03
02
01 00
08 07
04 03
00
2
1
0
16
16
16
08
2
16
00
0
16
375