Operating Procedure
Creating I/O Tables
If the unit number is set to 1, words will be allocated to the Special I/O Unit
Area CIO 2010 to CIO 2019 and to the Special I/O Unit Area D20100 to
D20199.
Note A single CS1W-AD161 is allocated CIO Area words and DM Area words for
two Units. For example, if the unit number is set to 1, the CS1W-AD161 will be
allocated CIO Area words CIO 2010 to CIO 2029 and DM Area words D20100
to D20299.
5. Turn ON the power to the PLC.
After turning ON the power to the PLC, be sure to create the I/O tables.
Section 2-2
Power ON
Peripheral port
23