Analog Input Functions and Operating Procedures
Note
Input signal
to the Unit (V)
Conversion data
Response Time for a
Resolution of 1 ms/4,000
322
4. With the fourth cycle, the Data 4 is stored in the first history buffer.
Data 4
Data 3
Data 2
Data 1
Mean value = (Data 4 + Data 3 + Data 2 + Data 1) ÷ 4
5. With the fifth cycle, Data 5 is stored in the first history buffer.
Data 5
Data 4
Data 3
Data 2
Mean value = (Data 5 + Data 4 + Data 3 + Data 2) ÷ 4
When a disconnection is restored, the mean value processing function begins
again from step 1.
1. When the mean value processing function is used, the delay in refreshing
converted data for input signal changes will be as shown in the following
diagram.
2. Specify "no mean value processing" to follow conversion of a rapid change
in input signals.
Time (ms)
Time (ms)
t: Delay
Unit: ms
m
64
4
258.5
130.5
3
196.5
100.5
2
134.5
70.5
1
67
35
(Mean value
processing)
(Mean value
processing)
For V = 20 V ( − 10 to 10 V)
When Resolution is 1 ms/4,000
• For One Word
t = n + (2 to 3)
• For m Words (1 < m ≤ 4)
No averaging (n = 1) or two averaging buffers (n = 2)
t = n × (m + 2)
For n averaging buffers (4 ≤ n ≤ 64)
t = (n − 2) × m + 10.5
When Resolution is 500 µ s/8,000
• For One Word
t = [n + (2 to 3)] × 1/4
• For m Words (1 < m ≤ 4)
No averaging (n = 1) or two averaging buffers (n = 2)
t = n × (m + 2) × 1/2
For n averaging buffers (4 ≤ n ≤ 64)
t = [(n − 2) × m + 10.5] × 1/2
n
32
16
8
66.5
34.5
52.5
28.5
38.5
22.5
19
11
Section 7-6
Conversion value
Conversion value
4
2
18.5
12
6
16.5
10
5
14.5
8
4
7
5
3
1