Omron CS1W-AD041-V1 Operation Manual page 257

Sysmac cs/cj series
Table of Contents

Advertisement

Operating Procedure
Output 1: 1 to 5 V. Set to 10.
Output 2: 1 to 5 V. Set to 10.
Output 3: –10 to 10 V. Set to 00.
Output 4: Not used. Set to 00 (disabled).
m+1: DM20101
(A60A Hex)
Creating Ladder Programs
1,2,3...
234
• The following diagram shows the input and output range settings. Re-
fer to 6-6-1 Input Settings and Conversion Values or 6-7-1 Output Set-
tings and Conversions for more details.
Bit
15
14 13
12 11 10
1
0
1
0
0
2. Restart the CPU Unit.
1. The following example describes how to use analog inputs.
The data that is converted from analog to digital and output to CIO words (n +
5) to (n+ 8) of the Special I/O Unit Area (CIO 2015 to CIO2018), is stored in
the specified addresses D00100 to D00103 as signed binary values 0000 to
0FA0 Hex.
09 08 07
06 05
04 03
1
1
0
0
0
0
0
Input 1: 1 to 5 V. Set to 10.
Input 2: 0 to 10 V. Set to 01.
Input 3: 4 to 20 mA. Set to 10.
Input 4: 4 to 20 mA. Set to 10.
Power turned ON again
(or Special I/O Unit Restart Bit is turned ON)
Section 6-2
02
01 00
1
0
1
0
Peripheral port