Omron CS1W-AD041-V1 Operation Manual page 87

Sysmac cs/cj series
Table of Contents

Advertisement

Adjusting Offset and Gain
64
Wiring for Voltage Input
CS1W-AD041-V1/081-V1
A1
A2
A3
CS1W-AD161
+
Voltage n
Wiring for Current Input
When using current input, short-circuit the input (+) terminal and the current
mode terminal.
CS1W-AD041-V1/081-V1
A1
A2
A3
For current input, check that the voltage/
current switch is ON.
CS1W-AD161
+
Current input n
3. Input the voltage or current so that the conversion value becomes 0000.
The following table shows the offset adjustment voltages and currents to
be input according to the input signal range.
Input signal range
0 to 10 V
–10 to 10 V
1 to 5 V
0 to 5 V
4 to 20 mA
Voltage input
+
Input 1
Input n+
Current mode n
Input n−
Shield
AG
Current input
+
Input 1
Input n+
Current mode n
Input n−
Shield
AG
Input range
–0.5 to 0.5 V
–1.0 to 1.0 V
0.8 to 1.2 V
–0.25 to 0.25 V
3.2 to 4.8 mA
Section 2-7
Word (n+8) monitoring
value
FF38 to 00C8 (4,000 res-
olution)
FE70 to 0190 (8,000 res-
olution)