Fixed Data Allocations - Omron CS1W-AD041-V1 Operation Manual

Sysmac cs/cj series
Table of Contents

Advertisement

Exchanging Data with the CPU Unit
6-5-4

Fixed Data Allocations

DM Allocation and
Contents
SYSMAC CS-series CPU Unit
(Special I/O Unit DM Area)
Unit #0
Unit #1
Unit #2
Unit #3
Unit #4
Unit #5
Unit #6
Unit #7
Unit #8
Unit #9
Unit #10
~
D20000 + (n x 100) to
Unit #n
D20000 + (n x 100) + 99
~
Unit #95
Note
246
The initial settings of the Analog I/O Unit are set according to the data allo-
cated in the Special I/O Unit DM Area. Settings, such as the inputs and out-
puts used, the analog input signal range, and analog output signal range must
be set in this area.
Word
D20000 to D20099
D20100 to D20199
D20200 to D20299
Data is automatically
transferred to each unit
D20300 to D20399
number when the power
D20400 to D20499
is turned ON, or when
the Special I/O Unit
D20500 to D20599
Restart Bit is turned ON.
D20600 to D20699
D20700 to D20799
D20800 to D20899
D20900 to D20999
D21000 to D21099
~
~
D29500 to D29599
1. The Special I/O Unit DM Area words that are occupied by the Analog I/O
Unit are set using the unit number switch on the front panel of the Unit. Re-
fer to 6-3-2 Unit Number Switch for details on the method used to set the
unit number switch.
2. If two or more Special I/O Units are assigned the same unit number, a
"UNIT No. DPL ERR" error (in the Programming Console) will be generat-
ed (A40113 will turn ON) and the PLC will not operate.
CS1W-MAD44 Analog I/O Unit
(Fixed Data Area)
I/O conversion
permission loop
D(m)
mode setting
I/O signal range
D(m+1)
D(m+2 to
Output hold
m+5)
function setting
Sets number of
D(m+6 to
samples for mean
m+9)
value processing
D(m+10 to
Ratio set value,
m+17)
bias value setting
m = 20000 + (unit number x 100)
Section 6-5